Replacing A Heat Detector (Standard) - Huawei FusionModule 1000B Maintenance Manual

Air-cooled it solution
Table of Contents

Advertisement

FusionModule1000B Air-Cooled IT Solution
Maintenance Guide
Figure 6-44 Smoke detector installation reference line
Step 7 Power on the fire alarm control panel after verifying that the new smoke detector is properly
installed.
Step 8 Check whether the new smoke detector is working properly.
----End
Follow-up Procedure
Dispose of the removed smoke detector that is confirmed faulty.

6.4.2 Replacing a Heat detector (Standard)

Prerequisites
Impact on the System
The fire extinguishing system stops working during the replacement.
Preparations
Tools: protective gloves, step ladder, Phillips screwdriver
Materials: spare heat detector
Documents: fire extinguishing device layout diagram (standard)
Skill requirement: fire engineer
Issue 02 (2017-01-10)
If the red indicator blinks once every 6s, the smoke detector is working properly.
A heat detector needs to be replaced.
A spare heat detector of the same model is available and functional.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
6 Parts Replacement