Humidity Alarms - Huawei FusionModule 1000B Maintenance Manual

Air-cooled it solution
Table of Contents

Advertisement

FusionModule1000B Air-Cooled IT Solution
Maintenance Guide

5.5 Humidity Alarms

Fault
Category
Humidity
too high
Humidity
too low
Issue 02 (2017-01-10)
Air-cooled precision air conditioners include 20 kW and 35 kW models. When verifying
parameters, ensure that the initial configuration table of the correct model is obtained.
A high temperature may lead to fire or equipment damage. Therefore, a high temperature
alarm must be immediately handled as instructed by
Overtemperature. This section can be used as a reference only after the temperature
becomes normal.
Alar
Symptom
m
Sever
ity
Gener
The onsite humidity
al
is normal.
The onsite humidity
is too high.
Inform
The onsite humidity
ation
is normal.
The onsite humidity
is too low.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
7.5 Emergency Operations for
Possible
Troubleshooting
Cause
The T/H sensor
Replace by following
is faulty.
instructions in
Replacing a Polymer
T/H
The humidity
Verify that the
threshold is not
configured temperature
properly set.
and humidity thresholds
are consistent with the
T/H sensor initial
configuration table in the
initial configuration
parameter manual.
The load ratio is
Shut down some air
too low.
conditioners.
The T/H sensor
Replace by following
is faulty.
instructions in
Replacing a Polymer
T/H
The humidity
Verify that the
threshold is not
configured temperature
properly set.
and humidity thresholds
are consistent with the
T/H sensor initial
configuration table in the
initial configuration
parameter manual.
The
Troubleshoot by
humidification
following instructions in
function of air
the air conditioner user
conditioners is
manual.
abnormal.
5 Alarms and Faults
6.3.1
Sensor.
6.3.1
Sensor.
60