Huawei FusionModule 1000B Maintenance Manual page 40

Air-cooled it solution
Table of Contents

Advertisement

FusionModule1000B Air-Cooled IT Solution
Maintenance Guide
Item
Sealing
materials
between
combined
containers
External
cable trays
External
environmen
t of
containers
Issue 02 (2017-01-10)
Method
Expected
Result
or corrosion.
Check the sealing
The sealing
materials between
materials are
combined
intact and have
containers.
not aged.
Check whether the
Cables and
cables and cable
cable trays are
trays are intact.
intact without
serious aging.
Check whether
No hazard or
hazards or
potential
potential hazards
hazard exists
exist around the
around the
containers.
containers.
Check whether
No obvious
obvious rubbish
rubbish exists
exists around the
around the
containers.
containers.
Check whether the
The ambient
ambient
temperature,
temperature,
humidity, and
humidity, and solar
solar radiation
radiation outside
requirements
the containers meet
for the
requirements.
FusionModule
1000 are as
follows:
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Troubleshooting
Replace by following instructions in
the Installing Sealing Materials
Between Combined Containers
section in the installation guide for
the solution in use.
Replace seriously aged cables. For
details, see the installation guide for
the solution in use.
Take measures to handle potential
hazards.
Clean the rubbish.
For details, contact Huawei
technical support.
Temperatur
e: –40° C to
+52° C.
Humidity:
5%–95%
RH
Solar
radiation: ≤
2
1120 W/m
4 Routine Maintenance
32

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fusionmodule 1000