FusionModule1000B Air-Cooled IT Solution
Maintenance Guide
Procedure
Step 1 Locate the water sensor to be replaced based on the alarm information on the monitoring
software terminal.
Figure 6-16 Rope-type water sensor
Step 2 Remove the signal cable and extension cable.
Figure 6-17 Removing the signal cable and extension cable
Step 3 Remove the screws tightening the faulty water sensor using a Phillips screwdriver, and
remove the water sensor.
Step 4 Install a new water sensor and tighten the screws.
Step 5 Connect the signal cable and extension cable of the water sensor by following
reverse order.