Cooling System - Huawei FusionModule 1000B Maintenance Manual

Air-cooled it solution
Table of Contents

Advertisement

FusionModule1000B Air-Cooled IT Solution
Maintenance Guide
Item

4.3.2 Cooling System

If a cooling component needs to be powered off for maintenance, take measures to prevent
device overheating before powering off the component.
Table 4-4 Monthly maintenance checklist for the cooling system
Item
20 kW
air-cooled
precision
air
conditioner
Issue 02 (2017-01-10)
Method
Expected
Result
Method
Expected
Result
Check electric
The electric
heaters.
heaters and
switches are
secure.
The electric
heater surface
is not
corroded.
Check the floats.
There is no
scale.
The floats are
working
properly.
Check screws
The
securing the
compressor is
compressor.
securely
installed.
Check the service
The
valve.
compressor
service valve
has no oil
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Troubleshooting
temperature
is lower
than 45° C.
The
ambient
battery
temperature
is 25± 5° C.
Troubleshooting
Secure the electric heaters and
switches.
Replace the faulty electric heater by
following instructions in the air
conditioner user manual.
Clean the floats.
Replace the faulty float by
following instructions in the air
conditioner user manual.
Tighten screws securing the
compressor.
Clean the oil stains.
4 Routine Maintenance
24