Installation And Cable Connection; Installation Preparations - Huawei UPS2000-H Quick Manual

Hide thumbs Also See for UPS2000-H:
Table of Contents

Advertisement

UPS2000-H-(6 kVA-10 kVA)
Quick Guide
1

1.1 Installation Preparations

● A circuit breaker needs to be installed in the upstream of the UPS to facilitate
● If a single UPS is configured with lead-acid batteries, the leakage current of the
● When UPSs are connected in parallel, the output parallel power cables of each
● Check the lead-acid battery voltage range: Use a multimeter to measure the
● If the upstream input switch of the UPS is equipped with a residual current
Issue 03 (2023-08-20)

Installation and Cable Connection

NO TICE
maintenance.
6 kVA UPS and 10 kVA UPS is less than or equal to 50 mA, respectively. When
selecting a residual current circuit breaker, consider the leakage current of the
UPS and its downstream loads.
UPS must be at least 1 m long and the length deviation must be less than
±10%. The four cables must be connected at the remote end.
voltage between the positive and negative battery terminals. Voltage range: 9.6
V x Number of batteries to 14.4 V x Number of batteries. For example, if 20
batteries are installed, the voltage between the positive and negative battery
terminals should range from 192 V (20 x 9.6 V) to 288 V (20 x 14.4 V).
circuit breaker, you are advised to check the leakage current before installing
the UPS. The leakage current of the UPS is less than or equal to 50 mA. Ensure
that the system leakage current does not exceed the rated value of the
upstream residual current circuit breaker after the UPS is installed. Otherwise,
the circuit breaker may trip for protection. Example: The upstream residual
current circuit breaker for the UPS has a rated leakage current of 300 mA. The
system leakage current reaches 250 mA before UPS installation. The leakage
current of the UPS is less than or equal to 50 mA. After the UPS is installed, the
leakage current of the system may be greater than 300 mA (250 mA + 50 mA).
In this case, the upstream circuit breaker will trip for protection.