Table 21: Description Of Marking Example According To Atex And Iecex - WAGO 750-606 Manual

24 v dc 1.0 a power supply ex i, supply module 24 v dc, 1.0 a ex i for wago-i/o-system 750
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-606 24 V DC 1.0 A power supply Ex i

Table 21: Description of Marking Example According to ATEX and IECEx

Marking
TUEV 07 ATEX 554086 X
IECEx TUN 09.0001 X
Dust
II
3 D
Ex
tc
IIIC
T135°C
Dc
Mining
I
M2
Ex
d
I
Mb
Gases
II
3 G
Ex
nA
IIC
T4
Gc
Use in Hazardous Environments
Description
Approving authority resp. certificate numbers
Equipment group: All except mining
Category 3 (Zone 22)
Explosion protection mark
Type of protection: Protection by enclosure
Explosion group of dust
Max. surface temperature of the enclosure
(without a dust layer)
Equipment protection level (EPL)
Equipment group: Mining
Category: High level of protection
Explosion protection mark
Type of protection: Flameproof enclosure
Explosion group for electrical equipment for
mines susceptible to firedamp
Equipment protection level (EPL)
Equipment group: All except mining
Category 3 (Zone 2)
Explosion protection mark
Type of protection: Non-sparking equipment
Explosion group of gas and vapours
Temperature class: Max. surface temperature
135 °C
Equipment protection level (EPL)
Version 1.4.0 valid from HW version 03