Danfoss VLT AFE 302 Operating Instructions Manual page 51

Active front end
Hide thumbs Also See for VLT AFE 302:
Table of Contents

Advertisement

How to Programme
5.9 Parameters: 16-** Data Read-outs
5.9.1 16-0* General Status
16-00 Control Word
Range:
0
[0 - FFFF] View the Control word sent from the AFE via the
*
16-03 Status Word
Range:
5
5
0
[0 - FFFF] View the Status word sent from the AFE via the
*
5.9.2 16-3* AFE Status
16-30 DC Link Voltage
Range:
0 V
[0 - 10000 V] View a measured value. The value is filtered
*
16-34 Heatsink Temp.
Range:
[0 - 255 °C] View the AFE heatsink temperature. The cut-
0°C
*
16-35 Inverter Thermal
Range:
0 %
[0 - 0 %]
*
16-36 Inv. Nom. Current
Range:
A
[0.01 - 10000.00 A]
*
16-37 Inv. Max. Current
Range:
A
[0.01 - 10000.00 A]
*
16-39 Control Card Temp.
Range:
0 C
[0 - 100 C] View the temperature on the control card,
*
16-41 Current
Range:
0.00 A
[0.00 - 1856.00 A ] Returns the value of measured
*
16-42 Voltage
Range:
0.0V
[0.0 - 6000.0V] Shows the AFE output voltage when the
*
50
VLT
Function:
serial communication port in hex code.
Function:
serial communication port in hex code.
Function:
with an 30 ms time constant.
Function:
out limit is 90 ± 5°C, and the motor cuts back
in at 60 ± 5°C.
Function:
View the percentage load.
Function:
View the inverter nominal current.
Function:
View the inverter maximum current.
Function:
stated in °C.
Function:
current as a mean value IRMS.
Function:
AFE is running.
MG.33.X2.02 - VLT
®
Active Front End AFE 302 Operating Instructions Liebherr
16-43 Frequency
Range:
0.0 Hz
[0.0 - 6500.0 Hz] Returns the actual AFE frequency,
*
16-44 Power [kW]
Range:
0.00 kW
*
16-45 Power [hp]
Range:
0.00 hp
*
hp]
16-49 Current Fault Source
Range:
0
[0 - 8 ] Value indicates source of current faults including
*
5.9.3 16-6* Inputs and Outputs
16-60 Digital Input
Range:
0 N/
[0 -
A
1023 N/
*
A]
®
is a registered Danfoss trademark
Function:
when the AFE is running.
Function:
[0.00 - 1000.00 kW] Returns the calculated AFE power
on basis of the actual voltage and
current.
Function:
[0.00 - 1000.00
Returns the calculated AFE power
on basis of the actual mains voltage
and mains current.
Function:
short circuit, over current, and phase imbalance
(from left):
1-4 Inverter
5-8 Rectifier
0 No fault recorded
Function:
View the signal states from the active digital inputs.
Example: Input 18 corresponds to bit no. 5, '0' = no
signal, '1' = connected signal. Bit 6 works in the
opposite way, on = '0', off = '1' (safe stop input).
Bit 0
Digital input term. 33
Bit 1
Digital input term. 32
Bit 2
Digital input term. 29
Bit 3
Digital input term. 27
Bit 4
Digital input term. 19
Bit 5
Digital input term. 18
Bit 6
Digital input term. 37
Bit 7
Digital input GP I/O term. X30/4
Bit 8
Digital input GP I/O term. X30/3
Bit 9
Digital input GP I/O term. X30/2
Bit 10-63
Reserved for future terminals