How to Programme

5.8 Parameters: 15-** AFE Information

5.8.1 15-0* Operating Data
15-00 Operating Hours
Range:
Function:
0h
[0 - 2147483647 h] View how many hours the AFE has run.
*
The value is saved when the AFE is
turned off.
15-01 Running Hours
Range:
Function:
0h
[0 - 2147483647 h] View how many hours the AFE has run.
*
Reset the counter in 15-07 Reset Running
Hours Counter. The value is saved when
the AFE is turned off.
15-02 kWh Counter
Range:
Function:
0kWh
[0 - 2147483647
Registering the power consumption
*
kWh]
of the system as a mean value over
one hour. Reset the counter in
15-06 Reset kWh Counter.
15-03 Power Up's
Range:
Function:
0
[0 - 2147483647] View the number of times the AFE has been
*
powered up.
15-04 Over Temp's
Range:
Function:
0
[0 - 65535] View the number of frequency converter
*
temperature faults which have occurred.
15-05 Over Volt's
Range:
Function:
0
[0 - 65535] View the number of AFE overvoltages which have
*
occurred.
15-06 Reset kWh Counter
Option:
Function:
[0]
Do not reset
Select Do not reset [0] if no reset of the kWh
*
counter is desired.
[1]
Reset counter Select Reset [1] and press [OK] to reset the
kWh counter to zero (see 15-02 kWh Counter).
NOTE
The reset is carried out by pressing [OK].
®
VLT
Active Front End AFE 302 Operating Instructions Liebherr
15-07 Reset Running Hours Counter
Option:
[0]
[1]
5.8.2 15-2* Historic Log
View up to 50 logged data items via the array parameters in
this parameter group. For all parameters in the group, [0] is
the most recent data and [49] the oldest data. Data is logged
every time an event occurs. Events in this context are defined
as a change in one of the following areas:
Events are logged with value, and time stamp in msec. The
time interval between two events depends on how often
events occur (maximum once every scan time). Data logging
is continuous but if an alarm occurs, the log is saved and the
values can be viewed on the display. This feature is useful,
for example when carrying out service following a trip. View
the historic log contained in this parameter via the serial
communication port or via the display.
15-20 Historic Log: Event
Array [50]
Range:
0 N/A
®
MG.33.X2.02 - VLT
is a registered Danfoss trademark
Function:
Do not reset
*
Reset counter Select Reset [1] and press [OK] to reset the
Running Hours counter to zero (see
15-01 Running Hours). This parameter cannot
be selected via the serial port, RS-485.
Select Do not reset [0] if no reset of the
Running Hours counter is desired.
1.
Digital input
2.
Digital outputs (not monitored in this SW release)
3.
Warning word
4.
Alarm word
5.
Status word
6.
Control word
7.
Extended status word
Function:
[0 - 255 N/A] View the event type of the logged events.
*
5
5
47