Configuration
®
With EchoWave
connected to your computer, open the WebCal
Follow steps 3 to 6 to configure the transmitter using WebCal
open the help menu of WebCal
®
WebCal
, please contact a Flowline
®
on the WebCal
software, please refer to the WebCal
STEP 3 – SENSOR CONFIGURATION
Configures the Loop Fail-Safe, Output at Empty, Startup Condition, Probe Type and Dielectric Range.
Out of Range
Flowline suggests setting the Loop Fail-safe to
HOLD Last Value in application where the liquid
level falls below the end of the probe or rises
above the Max. Fill-H.
If the level only falls below the end of the
probe, then EMPTY can be used.
If the level only rises above the Max. Fill-H,
then FULL can be used.
Note: Never allow the liquid to rise into the top dead band of the sensor (within 4" from the top of the
threads.
MN300840 REV A8
®
for more instructions on WebCal
®
application engineer at (562) 598-3015. Note: For complete information
®
®
software by clicking on the WebCal
®
. Click "Help" in the lower right hand corner and
®
. If you need additional assistance using
manual located at flowline.com/webcal-software.
Section Five
®
icon.
29
|