TROUBLESHOOTING

PROBLEM
No LED.
LED flashes Red.
Sensor is locked on a level
above the true level.
Probe Length is greater than
physical length of the probe.
Liquid level is below the probe,
but the sensor indicates a high
or full level.
Liquid level is above the Max.
Fill-Height, but the sensor
indicates a low or empty level.
MN300840 REV A8
Sensor is not receiving power (10 to 30 VDC). Check wiring to the
sensor as well as the power supply.
Sensor cannot acquire a valid level reading. Make sure the sensor is
installed properly within the application and the probe is touching liquid.
Sensor is likely acquiring a false echo from some interference close to
the probe. Running an Empty Signal Scan should address this issue.
You may have received a probe that was cut from its original factory
setting. When Factory Reset is clicked in WebCal, the default restores
this original length. The correct physical length of the probe must be re-
entered and written to unit before the sensor is installed in your
application.
Change the Fail-Safe setting to Hold Last Value or Empty
Change the Fail-Safe setting to Hold Last Value or Full