Specifications - FlowLine EchoWave LG10 Series Manual

Guided wave liquid level transmitter
Hide thumbs Also See for EchoWave LG10 Series:
Table of Contents

Advertisement

Introduction
ELECTRICAL
Analog output:
Total load resistance:
Lower range value:
Upper range value:
Response time:
Supply voltage:
Current consumption:
Start-up time:
Cable terminals:
MEASUREMENT
Reference condition:
Accuracy:
Repeatability:
Resolution:
Probe type:
Rod:
Cable:
Coaxial:
Probe length
Rod:
Cable:
Coaxial:
Probe loading
Rod:
Cable:
Coaxial:
Top dead band:
Bottom dead band:
APPLICATION SPECIFICATIONS
Intended Installation:
Rod:
Cable:
Coaxial:
Dielectric [εr]
Conductivity:
Density:
MN300840 REV A8
4 to 20mA
< 250Ω
4.0mA (span 0%)
20.0mA (span 100%)
5s
10 to 30VDC (reverse-polarity protected)
<50mA at 24VDC
<6s
Terminal block [wires 16 to 26 AWG (solid or stranded)]
(dielectric constant [εr] =80, water surface, tank 01m, DN200 metal flange)
±3mm
<2mm
<2mm
4mm
4mm, type 7x19
17.22mm (NPS ⅜", sch. 10)
[can be ordered in 5mm (0.2") increments from the reference point]
0.61 to 3.0m (2' to 9.8')
1.0 to 5.5m (3.3' to 18')
0.61 to 3.0m (2' to 9.8')
Maximum lateral load:
Maximum tensile load:
Maximum lateral load:
100mm (4")
50mm (2")
Metallic tank or below grade concrete basin
Metallic tank or below grade concrete basin
Non-metallic, plastic, fiberglass or metallic tank or below grade concrete basin
>1.8
No restrictions
No restrictions
6Nm... (0.2kg at 3 m)
5kN
100Nm... (1.67kg at 6 m)
Step One
3
|