9.6 "Settings" menu

Navigation
"Home" > "Settings"
Press
and go to the "Settings" menu with
This menu offers the following options:
Setpoint
Operating mode
Control mode
Controller settings, not model A
FLOWLIMIT
Automatic Night Setback
Analog Input
Relay outputs
Setpoint influence
Bus communication
General settings.
Navigate between the submenus with
9.6.1 "Setpoint"
Navigation
"Home" > "Settings" > "Setpoint"
Setting
1. Press [OK].
2. Select digit with
3. Press [OK] to save.
You can set the setpoint with an accuracy of 0.1 metre. The head
against a closed valve is the setpoint.
Set the setpoint so that it matches the system. A too high setting
may result in noise in the system whereas a too low setting may
result in insufficient heating or cooling in the system.
Control mode
Proportional pressure
Constant pressure
Constant temperature
.
Constant curve
9.6.2 "Operating mode"
Navigation
or
.
"Home" > "Settings" > "Operating mode"
This menu offers the following options:
Setting
1. Select operating mode with
2. Press [OK] to save.
For detailed information about the operating modes, see section
8.2 Operating modes.
and
and adjust with
Normal
Stop
Min.
Max.
or
or
.
Measuring unit
m, ft
m, ft
°C, °F, K
%
.