13.2.1 Description of communication interface modules
Fieldbus
Module
protocol
CIM 050
GENIbus
CIM 100
LonWorks
CIM 200
Modbus RTU
CIM 300
BACnet MS/TP
CIM 500
Ethernet
Description
CIM 050 is a Grundfos communication
interface module used for
communication with a GENIbus
network.
CIM 100 is a Grundfos communication
interface module used for
communication with a LonWorks
network.
CIM 200 is a Grundfos communication
interface module used for
communication with a Modbus RTU
network.
CIM 300 is a Grundfos communication
interface module used for
communication with a BACnet MS/TP
network.
CIM 500 is a Grundfos communication
interface module used for data
transmission between an industrial
ethernet network and a Grundfos
product.
CIM 500 supports various industrial
ethernet protocols:
• PROFINET
• Modbus TCP
• BACnet/IP
• Ethernet/IP
Functions
CIM 050 has terminals for the GENIbus
connection.
CIM 100 has terminals for the LonWorks
connection.
Two LEDs are used to indicate the actual
status of the CIM 100 communication.
One LED is used for indication of correct
connection to the pump, and the other is
used to indicate LonWorks communication
status.
CIM 200 has terminals for the Modbus
connection.
DIP switches are used to select parity and
stop bits, to select transmission speed and
to set line termination.
Two hexadecimal rotary switches are used
to set the Modbus address.
Two LEDs are used to indicate the actual
status of the CIM 200 communication.
One LED is used for indication of correct
connection to the pump, and the other is
used to indicate Modbus communication
status.
CIM 300 has terminals for the BACnet
MS/TP connection.
DIP switches are used to set transmission
speed and line termination and to select the
custom Device Object Instance Number.
Two hexadecimal rotary switches are used
to set the BACnet address.
Two LEDs are used to indicate the actual
status of the CIM 300 communication.
One LED is used for indication of correct
connection to the pump, and the other is
used to indicate BACnet communication
status.
CIM 500 supports various industrial ethernet
protocols. CIM 500 is configured via the
built-in web server, using a standard web
browser on a PC.
See the specific functional profile on the
DVD-ROM supplied with the Grundfos CIM
module.