Control Functions; Quick Overview Of Control Modes - Grundfos MAGNA3 D Installation And Operating Instructions Manual

Hide thumbs Also See for MAGNA3 D:
Table of Contents

Advertisement

Available languages

Available languages

8. Control functions

8.1 Quick overview of control modes

AUTO
ADAPT
We recommend this control mode for most heating systems.
During operation, the pump automatically makes the necessary
adjustment to the actual system characteristic.
FLOW
ADAPT
The FLOW
control mode combines a control mode and a
ADAPT
function:
The pump is running in AUTO
The delivered flow from the pump will never exceed a selected
FLOW
.
LIMIT
Proportional pressure
This control mode is used in systems with relatively large pressure
losses in the distribution pipes.
The head of the pump will increase proportionally to the flow in the
system to compensate for the large pressure losses in the
distribution pipes.
Constant pressure
We recommend this control mode in systems with relatively small
pressure losses.
The pump head is kept constant, independent of the flow in the
system.
Constant temperature
In heating systems with a fixed system characteristic, for example
domestic hot-water systems, the control of the pump according to a
constant return-pipe temperature is relevant.
ADAPT
H
H
set1
A
1
H
auto_min
H
set2
A
A
3
2
H
25 %
Q
90 %
Q
max
max
H
fac
H
auto_min
Q
fac
H
H
set
H
set
2
H
H
For further
information, see
section
.
8.3.2 AUTO
ADAPT
Q
For further
information, see
section
.
8.3.3 FLOW
ADAPT
Q
For further
information, see
section
8.3.4 Proportional
pressure.
Q
For further
information, see
section
8.3.5 Constant
pressure.
Q
For further
information, see
section
8.3.6 Constant
temperature.
Q
21