Siemens SIMATIC S7-1500 System Manual page 280

Drive controller
Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Feature
PROFIBUS interfaces
DRIVE-CLiQ
Onboard I/Os
(assigned to the drive)
Onboard I/Os
(assigned to the con-
troller)
Other interfaces
SINAMICS Integrated
SINAMICS Integrated
CX32-2
Memory card
Firmware
Runtime licensing
Miscellaneous
Controls
Display
elements
Fan
Battery
SIMATIC Drive Controller
System Manual, 11/2019, A5E46600094-AA
SIMOTION D4x5-2 DP/PN
2 (master/slave)
4 ports (D425-2); 6 ports (D435-2, D445-2,
D455-2)
12 DI, 8 DI/DQ
8 DI/DQ, channel-by-channel as:
DI, DQ, measuring input, output cam
2 x USB (for device updates)
On basis of CU320-2
(no EPOS, no SINAMICS Web server)
Yes
CF card
For firmware and project
Firmware is located on the memory card
A common firmware file for controller and
SINAMICS Integrated
With licensed memory card
2 rotary switches (mode selector; service se-
lector switch)
Diagnostics button; reset button
10 LEDs for controller and SINAMICS Inte-
grated
PN interfaces with LINK/Activity LED
7-segment display
Yes (dual fan for redundancy)
Yes
(required for buffering date/time > 4 days)
Information for users changing from SIMOTION D4x5-2
A.1 Information for users changing from SIMOTION D4x5-2
SIMATIC Drive Controller
1 (master)
Note: PROFIBUS cannot be operated in isoch-
ronous mode at the same time as other bus
systems on MC Servo.
4 ports
12 DI, 8 DI/DQ
Terminal type and terminal assignment as
SIMOTION D4x5-2
8 DI/DQ, channel-by-channel as:
DI, DQ, Timer DI (for measuring inputs), Timer
DQ (for output cams), Oversampling DI, Over-
sampling DQ, PWM, Event/period measurement
DQ can be operated as high-speed output
Terminal type and terminal assignment as
SIMOTION D4x5-2
2 x USB (no assigned function)
On basis of CU320-2
(no EPOS, no DCC/DCB, no free function
blocks, no SINAMICS Web server)
No, expansion with CU320-2 PN
SD card (SIMATIC Memory Card)
Can be used as program card or firmware up-
date card
Firmware is located on the Drive Controller
Separate firmware update files for controller and
SINAMICS Integrated
With engineering (Startdrive)
Toggle switch (mode selector)
Function button (for example, for diagnostics)
3 LEDs for controller / 3 LEDs for SINAMICS
Integrated
PN interfaces with LINK/Activity LED
LED for memory card access
7-segment display
No
No
(buffering date/time > 6 weeks)
279