SAEx 07.2
SAEx 16.2 / SAREx 07.2
Technical data
5.2.1.
Terminal compartment: open
SAREx 16.2
KP version (standard) with three cable entries. KPH version (enlarged) with additional
cable entries. Cable entries via the cover.
The terminal compartment (with screw-type terminals) is designed in protection type
Ex e (increased safety). Plug-in connection is made via the frame. Removing the
cover is sufficient for connecting the cables. The flameproof frame remains connected
to the device. The flameproof interior of the connected device remains sealed.
Table 9:
KP/KPH electrical connection
No. of contacts max.
Designations
Connection voltage max.
Rated current max.
Type of customer connection
Connection diameter max.
Figure 18: Open terminal compartment
[1]
Cover (figure shows KP version)
[2]
Screws for cover
[3]
O-ring
[4]
Blanking plugs
[5]
Cable gland (example)
[6]
Flameproof frame
Hazardous voltage!
Risk of electric shock.
Disconnect device from the mains before opening.
1.
Loosen screws [2] and remove cover [1].
Information: The terminal compartment is designed in protection type Ex e
(increased safety). The flameproof interior of the connected device remains
closed when removing the cover [1].
Power contacts
Control contacts
3 + protective earth conduct-
38 pins/sockets + protective earth con-
or (PE)
ductor (PE)
1 to 24, 31 to 40, 47 to 50, PE
U1, V1, W1,
(PE)
550 V
250 V
25 A
10 A
Screw connection
Screw connection
2
6 mm
1.5 mm
Electrical connection
2
23