6.3.1 Maintenance card

Inspection/maintenance pumping station Aqualift F XL
Name of the building
Building
Street
Postcode, city
Contact
System variant
Serial number
Pump type
Maintenance safety notes
Before opening the wastewater tank, ensure the room is sufficiently ventilated. Keep sources of ignition away
and do not smoke. Make sure that the pump(s) are at ambient temperature.
Inlet and outlet pipes must be emptied and pressure-less before work is started. The level in the wastewater
tank must be below the attachment level (pump flange) of the wastewater pumps. Aggressive cleaning agents
can damage seals. Use hot water and a brush for cleaning work.
Maintenance work according to EN 12056-4 and DIN 1986 Part 3
No.
Visual inspection
1
System installation complies with the above-mentioned standard and manufacturer's
specifications (as far as can be seen)
2
Fault message pending?
3
Function given
4
Isolate the system (disconnect the mains plug)!
5
Pressure switch
5.1
Remove the immersion pipe and clean it, remove the pump and clean the tank
5.2
Visual check pressure switch
5.3
Rising routing of the control pipe (constant gradient)
5.4
Immersion pipe
2016/05