4.14.5. RTD.LO - Calibrating minimum resistance value

Acronym
RTD.LO
The parameter appears if you are calibrating a custom I.MAIN RTD input.
To calibrate:
apply a resistance corresponding to minimum scale value to the main input (for example, 18.52 Ω for Pt100 ;
press the
key to acquire the calibration value.
Unit of measurement:
Options:
-

4.14.6. RTD.HI - Calibrating maximum resistance value

Acronym
RTD.HI
The parameter appears if you are calibrating a custom I.MAIN RTD input.
To calibrate:
apply a resistance corresponding to maximum scale value to the main input (for example, 390.48 Ω for Pt100);
press the
key to acquire the calibration value.
Unit of measurement:
Options:
-

4.14.7. C.LO - Setting analog output minimum

Acronym
C.LO
The parameter shows and sets the minimum analog output value.
You can change the displayed value with the
To check the real voltage/current value on the output during calibration, measure it with a voltmeter/ammeter.
Unit of measurement:
Options:
0...65535

4.14.8. C.HIG - Setting analog output maximum

Acronym
C.HIG
The parameter shows and sets the maximum analog output value.
You can change the displayed value with the
To check the real voltage/current value on the output during calibration, measure it with a voltmeter/ammeter.
Unit of measurement:
Options:
0...65535
Scrolling message
-
Scrolling message
-
Scrolling message
and
Converter points
Scrolling message
and
Converter points
80224_MHW_650 L - 1250 L_07-2018_ENG - 69
keys.
keys.
4. CONFIGURATION
Submenu
Attributes
US.CAL
R W
Submenu
Attributes
US.CAL
R W
Submenu
Attributes
US.CAL
R W
Submenu
Attributes
US.CAL
R W