3.4.

Setting up quick configuration

The quick configuration menu lets you quickly configure
and start an indicator.
To do this, it uses default values for many of the parameters
assigned to the functions.
With this configuration, the indicator can satisfy the majority
of operating requirements.
You can set up the first configuration with the main configu-
3.4.1.

Setting up the Alarm

If at least one output was configured as Alarm in the fast configuration.
0000
Home page
0000
Press > 2 seconds
0
Enter password (default = 1) with the
PASS1
Press until "ALARM" is displayed
ALARM
Submenu
ALARM
ALARM
d.i.x
A.r.x
HYSTE
MSG.AL
0000
Home page
0000
The ALARM submenu also lets you:
select the method for applying hysteresis (parameter
n.S.x, default = NORML);
enable or disable the power-on alarm (parameter
PWON.E, default = OFF);
latch/not latch the active alarm state (parameter LA-
TCH, default = OFF);
and
Select the Alarm number (default = 1) with the
Description of parameter and list of options on page. 77
Press twice
Set the alarm as direct or inverse (default = Direct) with the
Description of parameter and list of options on page. 77
Set the alarm as absolute or deviation (default = Absolute) with the
Description of parameter and list of options on page 77
Press 4 times
Set hysteresis (default = -1) with the
Description of parameter and list of options on page 79
Press twice
Select the message assigned to the alarm (default = 0) with the
Description of parameter and list of options on page 79
Press > 2 seconds
80224_MHW_650 L - 1250 L_07-2018_ENG - 29
ration menu (see paragraph "4.1. Programming/Configura-
tion Menu" on page 30), which gives access to all of the
parameters.
For purposes of example, some of the indicator's main fun-
ctions are listed below, with a list of parameters to be chan-
ged after running fast configuration to configure the indicator
to specific working conditions.
keys
and
and
keys
set the alarm trip delay (parameter DELAY, default
= 0.00);
activate or deactivate flashing of the PV display in case
of alarm (parameter BLK.AL, default = OFF).
3. COMMISSIONING
keys
and
keys
and
keys
and
keys