DLm8500 with PowerMax Physical Planning
DLm power requirements
Specification
Input voltage
Frequency
Circuit breakers
Power zones
Power requirements at customer site (for each
cabinet)
Power distribution panel connectors
Disk Library for mainframe Physical Planning Guide for DLm8500
38
This section describes the North American electrical specifications, power cables,
connectors, and extension cords for the VTEC cabinet in a DLm configuration.
The Dell EMC PowerMax Family Site Planning Guide provides further information about
power requirements for PowerMax system and storage cabinets.
The following table summarizes the North American, single-phase, electrical
specifications power requirements specific to a single VTEC cabinet:
Table 16 North American, single-phase, electrical specifications
Requirements
200 V AC to 240 V AC -10%/+10% single-phase
50 Hz to 60 Hz
30 A
Two
Two single-phase drops each for: DLm8500 VTEC cabinet
with up to one fully loaded
NEMA L6-30P, and the Facility power mating receptacle
is L6-30R.
Before delivery, the customer must supply and install the required receptacles to zone
A and zone B power for the DLm cabinets. The following figure shows the required
power cabling for DLm8500 systems: