Dlm8500 Physical Data Requirements; Dlm Power Requirements; Dlm Physical Specification For A Single Cabinet - Dell EMC DLm8500 Data Domain Physical Planning Manual

Disk library for mainframe
Hide thumbs Also See for DLm8500 Data Domain:
Table of Contents

Advertisement

DLm8500 Physical Data Requirements

DLm power requirements

Note
If you need to resolve errors, before continuing, you must contact EMC Support for
assistance to determine which port to open.
A single-rack DLm8500 weighs 1329 lb (603 kg).
DLm8500 multi-rack solution has a maximum configuration of one VTEC cabinet and
two DD6800, DD9300, or DD9800 cabinets.
When fully configured, the weight of each cabinet is:
VTEC cabinet— 1,060 lb (480.81kg)
l
Data Domain cabinet— 1,366 lb (619.61 kg)
l
DD storage cabinet — 1225lb (556.82 kg)
l
Note
All weight values are calculated for a fully loaded configuration. Contact your EMC
Sales Representative for specific supported configurations.
Despite the differences in weight, the physical dimensions of all the cabinets are the
same.
The following table lists the physical specifications for DLm cabinets.
Table 5 DLm physical specification for a single cabinet
Description
Height
Width
Depth
Clearance for service and airflow
Front
Rear
Top
a.
With trim kit (optional) attached.
This section describes the North American electrical specifications, power cables,
connectors, and extension cords for a DLm configuration.
The following table summarizes power requirements for the possible cabinets
associated with a DLm8500 system.
DLm8500 with Data Domain Physical Planning
Measurements
a
76.66 in (194.7 cm)
24.02 in (61.0 cm)
41.88 in (106.4 cm)
42 in (106.7 cm)
42 in (106.7 cm)
18 in (45.7 cm)
DLm8500 Physical Data Requirements