DLm power requirements
Table 8 DLm physical specification for a single cabinet
Description
Height
Width
Depth
Clearance for service and airflow
Front
Rear
Top
a.
With trim kit (optional) attached.
This section describes the North American electrical specifications, power cables,
connectors, and extension cords for a DLm configuration.
The following table summarizes power requirements for the possible cabinets that are
associated with a DLm8500 system.
Table 9 North American, single-phase, electrical specifications
Specification
Input voltage
Frequency
Circuit breakers
Power zones
Onsite power requirements (for each cabinet)
Power distribution panel connectors
Before delivery, the customer must supply and install the required receptacles to zone
A and zone B power for the DLm cabinets. The following figure shows 2-drop and 4-
drop power cabling.
Disk Library for mainframe Physical Planning Guide for DLm8500
DLm8500 with Data Domain Physical Planning
Measurements
a
76.66 in (194.7 cm)
24.02 in (61.0 cm)
41.88 in (106.4 cm)
42 in (106.7 cm)
42 in (106.7 cm)
18 in (45.7 cm)
Requirements
200 V AC–240 V AC -10%/+10% single-phase
50 Hz–60 Hz
30 A
Two
Two single-phase drops each for:
l
DLm8500 VTEC cabinet
Data Domain cabinet
Note:
For required power drops, see the
Power Calculator at
https://
powercalculator.emc.com
applicable documentation.
NEMA L6-30P. Facility power mating
receptacle is L6-30R.
and to any
31