FEMA ELECTRÓNICA . Series S . S40-T

1.8 Technical specifications

Digits
number of digits
led
color
digit height
Reading
overrange
underrange
in case of sensor break
Signal ranges
Accuracy at 25 ºC
Thermal drift
Signals accepted
temperature scale
units
Pt100 / RTD
resolution
ranges
max. error at 25ºC
offset drift
span drift*
(*span drift includes offset drift)
cable compensation
readings
Sensor
Range (en ºC)
Pt100 / RTD
800 / -200 ºC
Thermocouple J
1200 / -200 ºC
Thermocouple K
1372 / -200 ºC
Thermocouple T
400 / -200 ºC
Thermocouple E
1000 / -200 ºC
Thermocouple S
1768 / -50 ºC
Thermocouple R
1600 / -50 ºC
Thermocouple N
1300 / -200 ºC
Thermocouple C
2320 / 0 ºC
Thermocouple L
900 / -200 ºC
Thermocouple X
4000 / -200 ºC
Table 1 - Technical specifications for each sensor
4
4
7 segments led
red or green
14 mm
9999 with flash reading
-1999 with flash reading
reading 'to_high' or 'to_low' (see section 1.11.2)
(see Table 1)
(see Table 1)
(see Table 1)
Pt100 / RTD (see Table 1)
thermocouples (see Table 1)
ITS90
ºC or ºF, configurable
2 or 3 wires, configurable
1º or 0.1º, configurable
(see Table 1)
(see Table 1)
(see Table 1)
(see Table 1)
automatic up to 14 Ohms
4 / second
Error max.
at 25 ºC
<0.2 ºC
<2 ºC
<2 ºC
<2 ºC
<2 ºC
<4 ºC
<4 ºC
<2 ºC
<2 ºC
<2 ºC
<2 ºC
Thermocouples
resolution
ranges
max. error at 25 ºC
offset drift
span drift*
(*span drift includes offset drift)
thermocouple CJC
cold junction accuracy
cold junction drift
readings
Power
power 'H'
power 'L'
isolation*
consumption
Configuration
Front protection
Output and control options relays, analog outputs, serial communi-
Range (en ºF)
1562 / -328 ºF
2192 / -328 ºF
2372 / -328 ºF
752 / -328 ºF
1832 / -328 ºF
2282 / -58 ºF
2912 / -58 ºF
2372 / -328 ºF
4192 / 32 ºF
1652 / -328 ºF
7232 / -328 ºF
J, K, T, E, S, R, N, C, L and X
(thermocouple X is 10 uV/ºC linear signal)
(see Table 1)
(see Table 1)
(see Table 1)
(see Table 1)
automatic (see section 1.11.2)
<1.0 ºC
<0.04 º/ºC
3 / second
85 a 265 Vac/dc
11 a 60 Vdc y 24/48 Vac
2500 Veff with power 'H'
1500 Veff with power 'L'
*all units tested during 60 seconds
<1.5 W only meter
<4.0 W meter with options
3 buttons front keypad
(and rear jumper)
IP54
cations, ... (see section 2)
Offset drift
Span drift*
*includes offset drift
0.05 º/ºC
0.05 º/ºC
0.05 º/ºC
0.02 º/ºC
0.05 º/ºC
0.20 º/ºC
0.20 º/ºC
0.05 º/ºC
0.02 º/ºC
0.05 º/ºC
0.02 º/ºC
0.10 º/ºC
0.20 º/ºC
0.20 º/ºC
0.02 º/ºC
0.20 º/ºC
0.20 º/ºC
0.20 º/ºC
0.20 º/ºC
0.02 º/ºC
0.20 º/ºC
0.02 º/ºC