Series M . M60-C1
Impulse counter, ratemeter
PANEL MEtErS
Impulse counter, ratemeter and periodmeter, with 14 mm digit height. Accepts all type of impulse
sensors (NPN, PNP, Namur, TTL, inductive, mechanical, encoders, ...). Provides configurable excitation
voltage to power-up the transducer. Standard 96 x 48 mm size (1/8 DIN). Reading with 6 digit display.
Fast access to alarm setpoints, special modes for fast counting and for slow ratemeter applications,
'on power up' function, configurable reading brightness. Universal AC and DC power. Up to 3 optional
modules for output and control (relays, analog outputs, Modbus RTU communications, RS-485 ASCII,
RS-232, ...)
2975r09
ELECTRONICS
FOR
PANEL METERS . SIGNAL CONVERTERS . LARGE DISPLAYS
Tel. (+34) 93.729.6004 info@fema.es
User's Manual
INDUSTRIAL
AUTOMATION
www.fema.es

Advertisement

Table of Contents
loading

Summary of Contents for Fema M60-C1

  • Page 1 ELECTRONICS INDUSTRIAL AUTOMATION PANEL METERS . SIGNAL CONVERTERS . LARGE DISPLAYS Series M . M60-C1 Impulse counter, ratemeter PANEL MEtErS Impulse counter, ratemeter and periodmeter, with 14 mm digit height. Accepts all type of impulse sensors (NPN, PNP, Namur, TTL, inductive, mechanical, encoders, ...). Provides configurable excitation voltage to power-up the transducer.
  • Page 2: Table Of Contents

    Index 1. Panel meter M60-C1 ..... . 2 1.19.15 Menu ‘Key LE’ ....15 1.1 How to order .
  • Page 3: How To Order

    FEMA ELECTRÓNICA . Series M . M60-C1 1.1 How to order Model Power Option 1 Option 2 Option 3 Others -NBt (85-265 Vac/dc) (1 relay) (no buttons) (11/60 Vdc, (analog output) (front IP65) 24 Vac, 48 Vac) -RTU (Modbus RTU)
  • Page 4: Front View

    FEMA ELECTRÓNICA . Series M . M60-C1 1.6 Front view 1.9 Rear view Option 3 Option 1 Option 2 Alarms Logo Units 1 2 3 4 5 8 9 0 Units Signal Power Button ‘LE’ Button ‘UP’ Button ‘SQ’ (see section 3.2) (see section 1.7)
  • Page 5: Technical Specifications

    FEMA ELECTRÓNICA . Series M . M60-C1 1.11 Technical specifications Digits number of digits Counter Mode Frequency Section 7 segments led ‘FAST’ mode active max. 250 KHz 1.19.2 color red or green Counter digit height 14 mm normal mode max. 9 KHz 1.19.2...
  • Page 6: Function 'Trigger Sense

    FEMA ELECTRÓNICA . Series M . M60-C1 1.13 Function ‘Trigger Sense’ The trigger level is automatically configured when selecting a sensor from the ‘Sensor / Configuration’ (‘SnSr’ / ‘Auto’) menu list. the trig- ger level can be also manually modified from the ‘SnSr’ / ‘TrIG’ menu entry.
  • Page 7: How To Operate The Menus

    FEMA ELECTRÓNICA . Series M . M60-C1 1.17 How to operate the menus The instrument has two menus accessible to the user : Example of operation inside the ‘configuration menu’. ‘Configuration menu’ (key SQ) (<) 1. The SQ (<) key enters into the ‘Fast access’...
  • Page 8: Configuration Menu

    FEMA ELECTRÓNICA . Series M . M60-C1 1.19 Configuration menu 1.19.1 Initial set-up Press ‘SQ’ (<) for 1 second to access the ‘configuration menu’. For a description on how to operate inside the menus see section 1.17 . For a full vision of the ‘configuration menu’ structure see To configure the initial set up of the instrument, select the function 1.20...
  • Page 9: Configuration For 'Cnq.2

    FEMA ELECTRÓNICA . Series M . M60-C1 1.19 Configuration menu (cont.) 1.19.3 Configuration for ‘cnq.2’ Multiplier Configuration menu for mode ‘counter quadrature’ (‘cnq.2’). to- 1 to 999999 Multiplier tal impulses received are multiplied by the value of the ‘multiplier’ Conf. counter quadrature (‘MuLt’) register and divided by the ‘divider’...
  • Page 10: Configuration For 'Cnd.5

    FEMA ELECTRÓNICA . Series M . M60-C1 1.19 Configuration menu (cont.) 1.19.6 Configuration for ‘cnd.5’ Multiplier Configuration menu for mode ‘counter differential’ (‘cnd.5’). to- 1 to 999999 Configuration Multiplier tal impulses received are multiplied by the value of the ‘multiplier’...
  • Page 11: Configuration For 'Prd.8

    FEMA ELECTRÓNICA . Series M . M60-C1 1.19 Configuration menu (cont.) • select the ‘edges’ to count for each quadrature cycle (‘q.124’). Se- 1 imp. per cycle lect ‘1--1’ for 1 impulse per quadrature cycle. Select ‘1--2’ for 2 im- pulses per quadrature cycle.
  • Page 12 FEMA ELECTRÓNICA . Series M . M60-C1 1.19 Configuration menu (cont.) • ‘Pulls on channel A’ (‘PuL.A’) - activates pull resistors at chan- No pull resistor nel A. Select ‘P.uP’ to activate pull-up resistors (needed for NPN Pulls on channel A sensors).
  • Page 13: Alarms

    FEMA ELECTRÓNICA . Series M . M60-C1 1.19 Configuration menu (cont.) 1.19.11 Alarms Alarms The ‘Alarms’ (‘ALr’) menu configures the independent activation of up to 3 relay outputs, installed with the R1 optional modules (see section 2.1). For outputs up to 4 and 6 relays, see special modules r2,...
  • Page 14: Fast Access

    FEMA ELECTRÓNICA . Series M . M60-C1 1.19 Configuration menu (cont.) 1.19.12 Fast access The ‘UP’ (5) key at the front of the instrument gives access to a list Tools of functions configurable by the operator. See section 1.17 for an ex- planation on how to operate the ‘fast access’...
  • Page 15: Menu 'Key Le

    FEMA ELECTRÓNICA . Series M . M60-C1 1.19 Configuration menu (cont.) 1.19.15 Menu ‘Key LE’ No function The ‘LE’ (3) key at the front of the instrument can be configured to Key LE activate several functions. Only one function can be assigned to the ‘LE’...
  • Page 16: Full Configuration Menu

    FEMA ELECTRÓNICA . Series M . M60-C1 1.20 Full configuration menu Press ‘SQ’ (<) for 1 second to access the ‘Configuration menu’. See 1.19 section for a description of each menu entry. Multiplier Counter 1 to 999999 Multiplier Conf. counter...
  • Page 17 FEMA ELECTRÓNICA . Series M . M60-C1 1.20 Full configuration menu (cont.) Max. waiting time ‘SLOW’ mode Average filter Filter strength 1 to 1000 Sec. Average filter Filter strength Mechanical contact Sensor Automatic conf. Namur Multiplier NPN 2 wire 1 to 999999 Conf.
  • Page 18 FEMA ELECTRÓNICA . Series M . M60-C1 1.20 Full configuration menu (cont.) by rising edge Activation for Tools reset by falling edge Key UP Setpoint 1 (‘fast access’) Excitation voltage Setpoint 2 Setpoint 3 Memory of maximum Antirrebound filter (0 to 1000 mSec.)
  • Page 19: Factory Configuration

    FEMA ELECTRÓNICA . Series M . M60-C1 1.20 Full configuration menu (cont.) 1.21 Factory configuration Function counter (‘cn.1’) With left zeros Decimal point Counter configuration Left zeros Without left zeros Multiplier Divider Preset Mode Password ‘FAST’ Sensor Pulls on channel A...
  • Page 20: To Access The Instrument

    FEMA ELECTRÓNICA . Series M . M60-C1 1.22 To access the instrument You may need to access the inside of the instrument to add or re- place internal modules. Use a flat screwdriver to unlock the upper clips marked with ‘A’. Then unlock the lower clips marked with ‘B’ and remove the front cover.
  • Page 21: Precautions On Installation

    FEMA ELECTRÓNICA . Series M . M60-C1 1.24 Precautions on installation soon as power is connected. The instrument does not have protection fuse, Risk of electrical shock. Instrument terminals can be connected the fuse must be added during installation. to dangerous voltage.
  • Page 22: Output And Control Modules

    FEMA ELECTRÓNICA . Series M . M60-C1 2. Output and control modules 2.1 Module R1 2.2 Module AO The R1 module provides 1 relay output to M Series panel meters. The AO module provides 1 analog output with 4/20 mA or 0/10 Vdc Up to a maximum of 3 R1 modules can be installed in a single instru- configurable output range.
  • Page 23: Module Rtu

    FEMA ELECTRÓNICA . Series M . M60-C1 2.3 Module RTU 2.4 Module S4 The RTU module provides a Modbus RTU communications module The S4 module provides a RS-485 communications module for M for M Series of panel meters. The RTU module implements function Series of panel meters.
  • Page 24: Module S2

    FEMA ELECTRÓNICA . Series M . M60-C1 2.5 Module S2 2.6 Modules R2, R4, R6 The S2 module provides a RS-232 communications module for M The R2, R4 and R6 modules provide 2, 4 and 6 relay outputs for M Series of panel meters.
  • Page 25 FEMA ELECTRÓNICA . Series M . M60-C1...
  • Page 26: Other Options

    FEMA ELECTRÓNICA . Series M . M60-C1 3. Other options 3.1 Option NBT 3.3 Option G Instruments without front key- Green led digits option. pad. To configure the instrument, remove the meter from the panel and remove the front filter. Inter- nal press buttons for configuration are accessible.
  • Page 27: Accessories

    FEMA ELECTRÓNICA . Series M . M60-C1 4. Accessories 4.1 THM benchtop housing 4.3 Adapter DRA-M Benchtop housing for M Series Adapter for DIN rail mount, for and K Series panel meters. Handle M Series and K Series panel me- with three selectable positions.