Precautions On Installation; Factory Configuration; Warranty; Ce Declaration Of Conformity - Fema S Series User Manual

Panel meter for temperature signals
Hide thumbs Also See for S Series:
Table of Contents

Advertisement

1.15 Precautions on installation

Risk of electrical shock. Instrument terminals can be connected
to dangerous voltage.
Instrument protected with double isolation. No earth connection
required.
Instrument conforms to CE rules and regulations.
This instrument has been designed and verified conforming to the 61010-1 CE Security
Regulation, for industrial applications.
Installation of this instrument must be performed by qualified personnel only. This manual
contains the appropriate information for the installation. Using the instrument in ways not
specified by the manufacturer may lead to a reduction of the specified protection level.
Disconnect the instrument from power before starting any maintenance and / or instal-
lation action.
The instrument does not have a general switch and will start operation as soon as power is
connected. The instrument does not have protection fuse, the fuse must be added during
installation.
The instrument is designed to be panel mounted. An appropriate ventilation of the in-

1.16 Factory configuration

Sensor
Temperature configuration
Pt100 / RTD resolution
Reading offset
Thermocouple CJC
On break
Alpha
Symbol 'º'
Alarms 1 and 2
Active
Type
Setpoint
Hysteresis
Activation delay
Deactivation delay
Setpoint 2
Inverted relay
Locked alarms
Display
Steps
Maximum memory
Minimum memory
Tools
'Fast access'
'On power-up'
Delay
Alarm 1
Alarm 2
Key LE
Password
Brightness

1.17 Warranty

This instrument is warranted against all manufacturing defects for a
period of 24 MONTHS from the shipment date. This warranty does
not apply in case of misuse, accident or manipulation by non-autho-
rized personnel. In case of malfunction get in contact with your local
provider to arrange for repair. Within the warranty period and after
examination by the manufacturer, the unit will be repaired or substi-
tuted when found to be defective. The scope of this warranty is lim-
ited to the repair cost of the instrument, not being the manufacturer
eligible for responsibility on additional damages or costs.
Pt100 / RTD 2 wires
0.1º
0 counts
on
to_h
385
oFF
off (disabled)
alarm as maximum
1000
0 counts
0.0 seconds
0.0 seconds
off
off
off
off
-1999
9999
off
0 seconds
off
off
no function
off
3
FEMA ELECTRÓNICA . Series S . S40-T
strument must be assured. Do not expose the instrument to excess of humidity. Maintain
clean by using a humid rag and do NOT use abrasive products such as alcohols, solvents,
etc.
General recommendations for electrical installations apply, and for proper functionality
we recommend : if possible, install the instrument far from electrical noise or magnetic
field generators such as power relays, electrical motors, speed variators, ... If possible, do
not install along the same conduits power cables (power, motor controllers, electrovalves,
...) together with signal and/or control cables.
Before proceeding to the power connection, verify that the voltage level available matches
the power levels indicated in the label on the instrument.
In case of fire, disconnect the instrument from the power line, fire alarm according to local
rules, disconnect the air conditioning, attack fire with carbonic snow, never with water.

1.18 CE declaration of conformity

Manufacturer
FEMA ELECTRÓNICA, S.A.
Altimira 14 - Pol. Ind. Santiga
E08210 - Barberà del Vallès
BARCELONA - SPAIN
www.fema.es - info@fema.es
Products
S40-T
The manufacturer declares that the instruments indicated comply with the
directives and rules indicated below.
Electromagnetic compatibility directive 2014/30/EU
Low voltage directive 2014/35/EU
Directive ROHS 2011/65/EU
Security rules EN-61010-1
Instrument
Fixed
Permanently connected
Pollution degree 1 and 2 (without condensation)
Isolation
Double
Electromagnetic compatibility rules EN-61326-1
EM environment Industrial
Immunity levels
EN-61000-4-2
By contact ±4 KV
By air ±8 KV
EN-61000-4-3
EN-61000-4-4
On AC power lines : ±2 KV
On DC power lines : ±2 KV
On signal lines : ±1 KV
EN-61000-4-5
Between AC power lines ±1 KV
Between AC power lines and earth ±2 KV
Between DC power lines ±1 KV
Between DC power lines and earth ±2 KV
Between signal lines and earth ±1 KV
EN-61000-4-6
EN-61000-4-8
30 A/m at 50/60 Hz
EN-61000-4-11 0 % 1 cycle
40 % 10 cycles
70 % 25 cycles
0 % 250 cycles
Emission levels
CISPR 11
Instrument Class A, Group 1
Barberà del Vallès November 2017
Xavier Juncà - Product Manager
According to directive 2012/19/EU, electronic equip-
ment must be recycled in a selective and controlled
way at the end of its useful life.
Criteria B
Criteria B
Criteria A
Criteria B
Criteria B
Criteria B
Criteria B
Criteria B
Criteria B
Criteria B
Criteria B
Criteria A
Criteria A
Criteria A
Criteria A
Criteria B
Criteria B
Criteria A
15