Menu 'On Power Up; Menu 'Key Le; Function 'Password; Factory Reset - Fema S Series User Manual

Panel meter for temperature signals
Hide thumbs Also See for S Series:
Table of Contents

Advertisement

FEMA ELECTRÓNICA . Series S . S40-T
1.11 Configuration menu (cont.)
On Power-Up
Key LE
Password

Factory reset

10
Delay
Seconds
Alarm 1
Alarm 2
No function
Alarm unlock

1.11.7 Menu 'On Power Up'

The 'On Power Up' ('on.Pu') menu configures functions to apply at
start-up. It applies only to instrument restart after power loss. It does
not apply to instrument restart due to change in configuration.
• parameter 'Delay' ('dLAy') assigns a waiting time in seconds. The
instrument waits the configured time before starting normal func-
tion. During this waiting time, the display shows all decimal points on
in flash mode, all alarms are in the state defined at the 'Alarm 1' and
'Alarm 1' entries, there is no signal acquisition and there is no com-
munications or control being performed. After the configured time is
over, the instrument starts in normal function. Delay value between
0 and 200 seconds.
Application - the start-up process for an automation system implies
that different parts of the system (engines, actuators, controllers, ...)
have different start-up times. The 'Delay' function gives time to the
instrument to wait until the slowest part of the system is fully func-
tional before executing actions on the system (signal reading, relay
activation, ...)
• the 'Alarm 1' ('ALr1') and 'Alarm 2' ('ALr2') parameters allow to de-
fine the status of the alarms while the instrument is starting from a
power loss. Select 'on' for active alarm, select 'oFF' for deactivated
alarm.

1.11.8 Menu 'Key LE'

The 'LE' (3) key at the front of the instrument can be configured to
activate several functions. Only one function can be assigned to the
'LE' (3) key
• the 'No function' ('nonE') value assigns no function.
• the 'Alarm unlock' ('A.Lck') value assigns the manual unlock of the
alarms function, for instruments with the 'Locked alarms' ('A.Lck')
function activated (see section 1.11.3)

1.11.9 Function 'Password'

At the 'Password' ('PASS') menu select a 4 digit code to block access
to the 'configuration menu'. Instrument configuration will not be ac-
cessible to non authorized personnel. To activate the 'Password' se-
lect 'on' and introduce the code.
The code will be requested when trying to access the 'configuration
menu' (key 'SQ' (<)). The 'fast access' menu is not password pro-
tected.
1.11.10 Factory reset
At the 'Factory reset' ('FAct') menu, select 'yes' to load the default
factory configuration for the instrument (see section 1.16).

Advertisement

Table of Contents
loading

This manual is also suitable for:

S40-t

Table of Contents