Fema S40-T User Manual

Series s40 panel meter 72x36mm size for pt100 / rtd for thermocouples
Hide thumbs Also See for S40-T:

Advertisement

Quick Links

Series S40
Panel Meters
Panel meter 72x36mm size
Model S40-T
Panel meter for Pt100/RTD (2 and 3 wires), and thermocouples J, K, T, E, S,
R, N, C, L and X with temperature display in degrees celsius (ºC) or fahrenheit
(ºF). Selectable Pt100/RTD resolution at 1º or 0.1º, and manual offset available.
Thermocouple measure with internal CJC selectable (enabled or disabled).
Selectable behavior in case of sensor break ('to_high' or 'to_low'). Reduced
housing 72x36mm DIN standard. Display in 4 digits and negative sign. Maximum
and minimum display memory, steps, alarms with single or double setpoints, 5
levels of brightness, ... Universal AC and DC power modules and up to 2 modules
for signal retransmission and control.
USER'S MANUAL
(2264R00)
for Pt100 / RTD
for Thermocouples

Advertisement

Table of Contents
loading

Summary of Contents for Fema S40-T

  • Page 1 Series S40 Panel Meters Panel meter 72x36mm size Model S40-T for Pt100 / RTD for Thermocouples Panel meter for Pt100/RTD (2 and 3 wires), and thermocouples J, K, T, E, S, R, N, C, L and X with temperature display in degrees celsius (ºC) or fahrenheit (ºF).
  • Page 2: Order Reference

    Using the instrument in ways not specified by the manufacturer may lead carbonic snow, never with water. to a reduction on the specified protection level. Disconnect the instrument from power before starting any maintenance and / or installation action. FEMA ELECTRÓNICA - Page 2...
  • Page 3: Front View

    Fuse - To comply with security regulation 61010-1, add to the power line a protection fuse acting as disconnection element, easily accessible to the operator and identified as a protection device. Power “H” fuse 250mA time-lag Power “L” fuse 400mA time-lag FEMA ELECTRÓNICA - Page 3...
  • Page 4: Technical Data

    0.02º/ºC 0.02º/ºC Thermocouple L 900 / -200 ºC <2ºC 1652 / -328 ºF 0.05º/ºC 0.20º/ºC Thermocouple X 4000 / -200 ºC <2ºC 7232 / -328 ºF 0.02º/ºC 0.02º/ºC Table 3 - Thermocouple and PT100/RTD specifications FEMA ELECTRÓNICA - Page 4...
  • Page 5: Mechanical Dimensions (Mm)

    (“Max/Min”), the setpoint, the hysteresis value, the activation delay and the value of setpoint2 (“Off” or the setpoint2 value). OptionX (OptX) - Type of module installed. If there is no module shows “nonE”. FEMA ELECTRÓNICA - Page 5...
  • Page 6: Configuration Menu

    Offset counts Offset Reset - Leaving the “Configuration Menu” forces a restart of to add the instrument, even in case of no changes in configuration. Thermoc. CJC Reading to high On break Reading to low Alpha FEMA ELECTRÓNICA - Page 6...
  • Page 7: Default Factory Configuration

    1000 Hysteresis 0 counts Memory of maxim. Delay 0.0 seconds Setpoint2 Maximum Reset of maxim. Display Steps Memory of maximum -9999 Memory of minimum 9999 Memory of minim. Tools Minimum Reset of minim. Password Brightness FEMA ELECTRÓNICA - Page 7...
  • Page 8: Input Menu

    The alarms configured as maximum are deactivated when the display is lower than the setpoint. The alarms configured as minimum have the inverse behavior. Setpoint (SEt) - Value from “9999” to “-1999”. Alarm set point. FEMA ELECTRÓNICA - Page 8...
  • Page 9: Tools Menu

    Ohms (higher than 850ºC for PT100/RTD measure), or 2) in case the third wire ohm is higher than 15 Ohm, or 3) thermo- couple measure is open circuit. Err.1 Password incorrect. Err.2 The instrument has detected an installed option but was unable to communicate. FEMA ELECTRÓNICA - Page 9...
  • Page 10: Accessing The Instrument

    Pollution degree 1 and 2 (without condensation) 70% 25 cycle Criteria B Isolation Double 0% 250 cycle Criteria B Emission rules Barberà del Vallès November 2011 61000-6-4 Generic rule of emission Daniel Juncà - Quality Manager FEMA ELECTRÓNICA - Page 10...
  • Page 11 User’s Manual S40-T FEMA ELECTRÓNICA - Page 11...
  • Page 12 Signal Converters Panel Meters 60&100mm digit & Isolators Standard 96x48mm www.fema.es ELECTRONIC INSTRUMENTATION FOR INDUSTRY FEMA ELECTRÓNICA, S.A. Altimira 14 - Pol. Ind. Santiga E08210 Barberà del Vallès BARCELONA - SPAIN Tel. (+34) 93.729.6004 - www.fema.es Fax (+34) 93.729.6003 - info@fema.es...