2.3 Module SSR

The SSR module provides 1 output to control SSR relays, to install at
digital panel meters from Series S, up to a maximum of 2 SSR con-
trols in a single meter.
Configuration is performed from the frontal keypad of the meter, by
setting the parameters at the alarm menu. Check the parameters of
at the alarm menu for full information.
The module provides +15 Vdc voltage and up to 45 mA.
Modules SSR can be ordered pre-installed into a Series S digital panel
meter, or standalone for delayed installation, as they do not require
soldering or special configuration.
Type of output
to control an SSR relay
Voltage output
15 Vdc
Max. current
45 mA
Isolation
1000 Vdc
Type of terminal
plug-in screw terminal, pitch 5.08 mm
Slots allowed
'Opt.1', 'Opt.2'
+15 Vdc 'C'
Schematic for SSR control module
Opt.1
A B C
Signal
For more information : http://fema.es/docs/4254_SERIES_M-K-S_
OPTIONS_manual_i.pdf
Relé SSR
'B'
'A'
Opt.2
A B C
Power
FEMA ELECTRÓNICA . Series S . S40-T

2.4 Module AO

The AO module provides 1 analog output with 4/20 mA or 0/10 Vdc
configurable output range. Output current loop configurable as ac-
tive (the instrument provides the excitation for the loop) or passive
(the loop is externally powered). Signal output proportional to the
instruments reading. Fully configurable scaling, in direct (positive
slope) or inverse (negative slope) scaling.
Up to a maximum of 2 analog output modules can be installed in a
single instrument, all outputs isolated between them and isolated
from the power and input signal circuits.
Configuration from instrument front keypad, through menu entries
'Opt.1' or 'Opt.2', depending on the position the module is installed.
The AO module can be ordered pre-installed into a Series S panel
meter, or standalone for delayed installation, as it does not require
soldering or special configuration.
Output ranges
4/20 mA active, 4/20 mA passive 0/10 Vdc
Accuracy (at 25 ºC)
<0.1% FS
Isolation
1000 Vdc
Slots allowed
'Opt.1', 'Opt.2'
Terminal A
Terminal B
Terminal C
Jumper M
Jumper V
Opt.1
M V
A B C
Signal
For more information : http://fema.es/docs/4254_SERIES_M-K-S_
OPTIONS_manual_i.pdf
Vexc
Signal in mA or Vdc
GND
closed for mA
closed for Vdc
Opt.2
M V
A B C
Power
17