Flow
Counter
1. Front view
Alarm led
1
2
&
Units
Key 'LE'
Key 'SQ'
1. Exit the menu
1. Enter into 'Configuration menu'
2. Validate parameter
Key 'UP'
1. Enter into 'Fast access'
2. Next value
2. Dimensions and panel cut-out 'mm' (in.)
Panel
44 mm
48 mm
cut-out
(1.74 in.)
(1.89 in.)
92 mm
(3.63 in.)
96 mm
91 mm
(3.78 in.)
(3.58 in.)
(includes terminal)
Detail of the female
terminal provided.
3. Panel mount
2
How to install the meter in a panel
1.
Remove the 2 blue fixation tabs from each side
of the unit.
2.
Insert instrument from the front of the panel
into panel cut out.
3.
Re-attached the 2 blue fixation tabs by sliding
each one along its rail on each side and push until
3
the tabs are tight onto the panel. If needed use a
flat screwdriver to push the tabs strongly to the
end.
50
Q
5
YEARS
ISO 9001
EN-61010-1
EN-61326-1
YEARS
1969-2019
Certified Quality
Security
Electromagnetic C.
Extended Warranty
Quick installation guide C60-FL
4. Installation and start-up
1.
Open the instrument (see section 3)
2.
Connect the signal, the power and the rear controls (see section 6)
3.
Configure the instrument from the 'Configuration menu' (see section 13)
4.
If you need additional information, see section 8.
EN-61326-1
Electromagnetic C.
Q
ISO 9001
Certified Quality
50
YEARS
1969-2019
5. How to order
Series
Model
Power
Option 1
Option 2
C60
-
FL
-
U
-
-
-U
-A1
-A2
(1 relay SPDT)
(1 relay SPDT)
(Universal
-S1
(Modbus RTU)
power supply
-M1
(analog
18...265  V ac/dc)
output 4/20mA)
-(empty)
-(empty)
6. Connections
Option 2
Option 1
Module A1 (relay)
Module A2 (relay)
Com.
Com.
NO
NO
NC
NC
G
H
I
A B C
16 mm
(0.63 in.)
Option 2
Option 1
G
H
I
A B C
75 mm
(2.95 in.)
1 2 3 4 5
8 9 0
+Vdc/Phase
(not connected)
8 mm
-Vdc/Neutral
(0.31 in.)
Power supply 18...265 Vac/dc
(50 / 60 Hz) (<2.5 W) (isolated)
Protection fuse values:
250 mA time-lag for power voltage > 50 Vac/dc
400 mA time-lag for power voltage < 50 Vac/dc
1 2 3 4 5
Control 1
resets the total flow value
Control 2
reads the background instrument
0 Vdc
common
Signal
input signal (impulses)
1
Vexc
excitation voltage (+15 Vdc @50 mA)
7. How to operate the menu
Key 'SQ' (<) - press the 'SQ' (<) key for 1 second to access the 'configuration menu'.
Inside the menu, the 'SQ' (<) key functions as a 'ENTER' key. It selects and accesses
the menu option currently displayed. At menus with numerical value entries, it vali-
dates the number displayed.
Key 'UP' (5) - the 'UP' (5) key gives access to the 'fast access' menu. Inside the
!
menus, it moves vertically through the different menu options. At menus with numeri-
cal value entries, it modifies the digit selected by increasing its value to 0, 1, 2, 3, 4,
5, 6, 7, 8, 9.
Key 'LE' (3) - inside the menus, the 'LE' (3) key functions as the 'ESCAPE' key. It
leaves the selected menu, and eventually, will leave the whole menu. When leaving
the 'configuration menu' with the 'LE' (3) key, the changed parameters are activated.
At menus with numerical value entries, the 'LE' (3) key allows to select the active
digit. To modify the value of the selected digit use the 'UP' (5) key.
Menu 'Rollback'
After 30 seconds without interaction from the operator, the instrument will rollback
Others
Customization
and leave the 'configuration menu' or the 'fast access' menu. All changes will be dis-
carded.
-
.
Example
-NBT
-XXXX
(no front
(customized
The menu example indicated below is for information purposes only, and may not
keypad)
execution under request)
match the actual menu of the instrument.
-65
(front IP65)
-(empty)
-(empty)
(1)
(6)
(2)
(5)
Input
(3)
(3)
(5)
(3)
Module M1 (4/20 mA)
(5)
Active output
Passive output
(3)
+15 Vexc.
4/20 mA
4/20 mA
Common
(5)
(6)
(3)
A B C
A B C
Module S1 (Modbus RTU)
(3)
(3)
B
A
Common
A B C
8. Additional documentation
User's manual C60-FL
fuse
Datasheet C60-FL
Quick installation guide C60-FL
CE declaration of conformity
Warranty
9. User's manual
If you need additional information, see section 8
to download the full User's Manual or check the
QR code for a direct download.
10. Configuration example
A flow sensor provides 'NPN' impulses, with a frequency proportional to the instant
flow, with a 'K factor' value of '1.241804' [impulses / liter].
Configure the instrument to read the instant flow in [m
and the total flow accumulated in [gallons] with 2 decimal points.
By default instant flow must be on display, and access to the total flow value will be
done by activating the rear connector terminal.
Reset of the total flow will be performed by pressing the front key left 'LE' (3).
1. Instrument main configuration
At the 'Instrument configuration' ('c.InS') section :
at 'Main instrument' ('MAIn') select 'rAtE'
at 'Sensor' ('SnSr') select 'NPN'
at ''K' Decimal point' ('K.dP') select 'X.xxxxx'
at ''K' Factor' ('K.Ftr') configure '1.24180' (the last digit '4' of the 'K factor' can not
be introduced)
Validate changes and exit the 'configuration menu'. At this moment, the instrument is
configured and reads instant flow meter, in [liters/second].
3. Scale the instant flow value to the desired units [m
At the 'Instant flow configuration' ('c.rAt') section :
at 'Time Base (Multiplier)' ('tIME') configure '3600' (3600 seconds in 1 hour)
at 'Divider' ('dIV') configure '1000' (1000 liters in 1 m
at 'Resolution' ('rESL') select 'XXXXX.x'
Example of operation inside the 'configu-
Validate changes and exit the 'configuration menu'. At this moment, the instrument is
ration menu'.
configured and reads instant flow, in [m
1. The 'SQ' (<) key enters into the 'con-
4. Scale the total flow value to the desired units [gallons]
figuration menu'.
(4)
Relation between liters and gallons is 1 liter = 0.2642 gallons.
2. The 'SQ' (<) key enters into the 'InP'
At the 'Total flow configuration' ('c.tot') section :
option menu.
at 'Multiplier' ('MuLt') configure '2642'
(4)
3. The 'UP' (5) key moves through the
at 'Divider' ('dIV') configure '10000'
menu options.
The total scaling factor is '2642' / '10000' = '0.2642'
(4)
4. The 'SQ' (<) key selects the desired
at 'Resolution' ('rESL') select 'XXXX.xx'
range and returns to the 'InP' menu.
Validate changes and exit the 'configuration menu'. At this moment, the instrument
(4)
5. The 'LE' (3) key leaves the actual menu
is configured and reads total flow in [gallons], with 2 decimals. To read the total ac-
level and moves to the previous menu
cumulated flow on display, close the rear contact 'contact 1'.
level.
5. Configure 'Key Left' (3) to reset the total flow value
6. The 'LE' (3) key leaves the 'configu-
At the 'Key Left' ('K.LE') section :
ration menu'. Changes are applied and
at 'Reset 'total'' ('rSt.t') select 'on'
saved at this moment.
Validate changes and exit the configuration menu. At this moment, the total flow val-
ue will reset to '0' when the key 'LE' (3) is pressed.
11. Regulations
This instrument conforms to the actual CE regulations. For a copy of the 'CE declaration
www.fema.es/docs/5046_C60-FL_manual_en.pdf
of conformity' see section 8. Applicable regulations are :
www.fema.es/docs/5058_C60-FL_datasheet_en.pdf
Security regulations EN-61010-1 ('Fixed' equipment, 'Permanently connected'. 'Dou-
www.fema.es/docs/5060_C60-FL_installation_en.pdf
ble' isolation.)
Electromagnetic compatibility regulations EN-61326-1
www.fema.es/docs/5047_CE-Declaration_C60-FL_en.pdf
This instrument does not provide a general mains switch and will start operation as
www.fema.es/docs/4153_Warranty1_en.pdf
soon as power is connected. The instrument does not provide protection fuse, and the
fuse must be added during installation.
User's Manual C60-FL
!
FEMA ELECTRÓNICA, S.A. | Manufacturing for Industrial Automation | www.fema.es . info@fema.es
Series C
www.fema .es
3
/hour] with 1 decimal point,
3
/hour]
3
)
3
/hour], with 1 decimal.
Risk of electrical shock. Instrument terminals can be connected to dan-
gerous voltage.
Instrument protected with double isolation. No earth connection
required.
Instrument conforms to CE rules and regulations.
According to directive 2012/19/EU, electronic equipment must be re-
cycled in a selective and controlled way at the end of its useful life.
Standard warranty of 2 years according to actual european legislation.
Free of cost warranty extension of 5 years, available at: http://www.
fema.es/garantia.asp

Advertisement

loading

Summary of Contents for Fema C Series

  • Page 1 Standard warranty of 2 years according to actual european legislation. Free of cost warranty extension of 5 years, available at: http://www. fema.es/garantia.asp YEARS ISO 9001 EN-61010-1 EN-61326-1 YEARS FEMA ELECTRÓNICA, S.A. | Manufacturing for Industrial Automation | www.fema.es . info@fema.es 1969-2019 Certified Quality Security Electromagnetic C. Extended Warranty...
  • Page 2 Reset on display Setpoint Counter overrange Flash ‘Cut-off’ reading Hysteresis ‘cut-off’ Brightness reading Password YEARS ISO 9001 EN-61010-1 EN-61326-1 YEARS FEMA ELECTRÓNICA, S.A. | Manufacturing for Industrial Automation | www.fema.es . info@fema.es 1969-2019 Certified Quality Security Electromagnetic C. Extended Warranty...

This manual is also suitable for:

C60-fl