3. Basic Operations for Periodic Inspection Work

All work other than when the STOP (all stop) switch (S001) is set to STOP and the VG (fuel solenoid valve forced off
switch) switch (S002) is set to OFF should be performed with the HOME (S004), SET (S007), UP (S005), and DOWN
(S006) keys.
It is extremely dangerous if the customer performs an operation that runs the engine during a maintenance inspection
or when not expected. Make sure you stop operation during work in the way described below.
* Pressing the HOME (S004) key for 1 second or more forcefully returns the state to the initial state. The
value of a partially set item will be discarded, and the item number will return to "
* If there is no operation for 10 minutes when other than the "
a partially set item will be discarded, and the item number will return to "
(1) Backup operation during maintenance work (for W MULTI)
What is backup operation?
In the GHP W MULTI series, multiple outdoor units are connected to the same refrigerant tube. Therefore,
even during maintenance work of an outdoor unit, the other outdoor unit not required in maintenance work can
be used to keep the indoor operating conditions. This is called a backup operation.
Backup operation procedure
To perform backup operation, the outdoor unit for maintenance work (hereafter referred to as "target outdoor
unit") must be cut off from the system using the following procedure. Review content of the maintenance work
and then select the most suitable method.Also, after the maintenance work is nished, always refer to [System
recovery procedure] and then return the system to its normal state.
[Backup operation procedure]
To turn off power of target outdoor unit and then perform maintenance work (basic operation during
inspection of outdoor unit)
<<Important>>
This is the basic operation performed during inspection work. If this operation is not performed and the
power of the outdoor unit is turned off, this will cause system fault and prevent backup operation to be
carried out, and serious malfunction will occur. If this happens, see [System recovery procedure] to recover
the system, and then once again use the following procedure to perform setup. Automatic backup operation
will kick in.
<<Step 1>>
On the outdoor main board of the target outdoor unit,
set the STOP switch (S001) to "STOP". *1
<<Step 2>>
(After con rming that the engine of the tar get outdoor
unit is stopped) close the valves of refrigerant gas tube,
refrigerant gas liquid tube, and balance tube.
<<Step 3>>
On the outdoor main board of the target outdoor unit,
set the STOP switch (S001) to "STOP". Wait for three
minutes or more and then turn off the circuit breaker of
the target outdoor unit. *2
Start maintenance work.