Power requirements

Self-switching AC/DC input, automatically recognizes supply voltage:
85 to 240 VAC, 50/60 Hz, 6 watts typical, 11 watts maximum
18 to 100 VDC, 6 watts typical, 11 watts maximum
Note
For DC power:
Power requirements assume a single transmitter per cable.
At startup, the power source must provide a minimum of 1.5 amps of short-term
current per transmitter and not pull voltage below 18 VDC.
Length and conductor diameter of the power cable must be sized to provide 18 VDC
minimum at the power terminals, at a load current of 0.7 amps.
Cable sizing formula
M = 18V + (R x L x 0.7A)
M: minimum supply voltage
R: cable resistance
L: cable length (in Ω/ft)
Installation Manual