Additional Considerations For Retrofitting Existing Installations; Power Requirements - Emerson Micro Motion 5700 Installation Manual

Hide thumbs Also See for Micro Motion 5700:
Table of Contents

Advertisement

Planning
February 2020
2.2
Additional considerations for retrofitting
existing installations
The transmitter installation may require 3 in (76 mm) to 6 in (152 mm) of additional
wiring for the input/output and power connections. This length would be in addition to
the currently installed wiring. Confirm you have the additional wiring necessary for the
new installation.
Before removing the existing transmitter, be sure to record the configuration data for
the currently installed transmitter. At initial startup of the newly installed transmitter,
you will be prompted to configure the meter via a guided setup.
Record the following information (if applicable):
Variable
Tag
Mass flow units
Volume flow units
Density units
Temperature units
Calibration parameters (for 9-wire installations only)
Flow calibration factor
Density calibration factors
Function block settings
Channel assignment
L_Type
XD_scale (engineering units
assignment)
2.3

Power requirements

Self-switching AC/DC input, automatically recognizes supply voltage:
85 to 240 VAC, 50/60 Hz, 6 watts typical, 11 watts maximum
8
Provides clear access for installing cabling to the transmitter.
Provides clear access to all wiring terminals for troubleshooting.
Setting
FCF (Flow Cal or Flow Calibration Factor):
D1:
D2:
K1:
K2:
TC:
FD:
Micro Motion 5700 transmitters for F
Installation Manual
MMI-20029969
Fieldbus
OUNDATION