5.2.13. Switches S201, S202, and S801
Switches S201 (A53) and S202 (A54) are used
to select a current (0-20 mA) or a voltage (0
to 10 V) configuration for the analog input
terminals 53 and 54, respectively.
Switch S801 (BUS TER.) can be used to enable
termination on the RS-485 port (terminals 68
and 69).
See drawing
terminals
Default setting:
Use a clamp from the accessory bag
to connect the shield to the adjusta-
ble frequency drive decoupling plate
for control cables.
Grounding of Shielded/
for the correct termi-
Diagram showing all electrical
in section
Electrical Installation.
S201 (A53) = OFF (voltage input)
S202 (A54) = OFF (voltage input)
S801 (Bus termination) = OFF
MG.11.B4.22 - VLT
®