7. RS-485 Installation and Set-up
Coil
ber
1-16
17-32
33-48
49-64
65
66-65536
7
Coil 0
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
Adjustable frequency drive control
word (FC profile)
150
Num-
Description
Adjustable frequency drive control word (see table be-
low)
Adjustable frequency drive speed or setpoint reference
Range 0x0 – 0xFFFF (-200% ... ~200%)
Adjustable frequency drive status word (see table below) Slave to master
Open-loop mode: Adjustable frequency drive output fre-
quency closed-loop mode: Adjustable frequency drive
feedback signal
Parameter write control (master to slave)
0 =
Parameter changes are written to the
RAM of the adjustable frequency drive.
1 =
Parameter changes are written to the
RAM and EEPROM of the adjustable fre-
quency drive.
Reserved
1
Preset reference LSB
Preset reference MSB
DC brake
No DC brake
Coast stop
No coast stop
Quick stop
No quick stop
Freeze freq.
No freeze freq.
Ramp stop
Start
No reset
Reset
No jog
Jog
Ramp 1
Ramp 2
Data not valid Data valid
Relay 1 off
Relay 1 on
Relay 2 off
Relay 2 on
Set-up LSB
Set-up MSB
No reversing
Reversing
MG.11.B4.22 - VLT
Signal Direction
Master to slave
Master to slave
Slave to master
Master to slave
Coil 0
33
Control not
ready
34
Adjustable fre-
quency drive not
ready
35
Coasting stop
36
No alarm
37
Not used
38
Not used
39
Not used
40
No warning
41
Not at reference At reference
42
Hand mode
43
Out of freq.
range
44
Stopped
45
Not used
46
No voltage warn-
ing
47
Not in current
limit
48
No thermal
warning
Adjustable frequency drive status
word (FC profile)
®
is a registered Danfoss trademark.
VLT
®
HVAC Drive Design Guide
1
Control ready
Adjustable fre-
quency drive
ready
Safety closed
Alarm
Not used
Not used
Not used
Warning
Auto mode
In frequency
range
Running
Not used
Voltage warning
Current limit
Thermal warning