2. Introduction to the VLT HVAC Drive
difference). If
to the PID controller, since this has the larger difference (feedback is lower than setpoint, resulting
in a positive difference).
2
2.8.9. Feedback Conversion
In some applications, it may be useful to convert the feedback signal. One example of this is using
a pressure signal to provide flow feedback. Since the square root of pressure is proportional to
flow, the square root of the pressure signal yields a value proportional to the flow. This is shown
below.
Another application that may benefit from feedback conversion is compressor control. In such
applications, the output of a pressure sensor may be converted to the refrigerant temperature
using the equation:
Temperature
where A1, A2 and A3 are refrigerant-specific constants.
46
Multi-setpoint Max
[13] is selected, the setpoint and feedback of Zone 2 are sent
A
2
=
(
(
+ 1 ) −
1 )
ln
pressure
A
MG.11.B4.22 - VLT
A
3
®
is a registered Danfoss trademark.
VLT
®
HVAC Drive Design Guide