Danfoss VLT Series Design Manual page 56

Hvac drive
Hide thumbs Also See for VLT Series:
Table of Contents

Advertisement

3. VLT HVAC Selection
Normal overload 110% for 1 minute
IP 21
IP 55
IP 66
Line supply 200-240 V AC
Adjustable frequency drive
Typical Shaft Output [kW]
3
Output current
Max. input current
56
Typical Shaft Output [HP] at 208 V
Continuous
(3 x 200-240 V) [A]
Intermittent
(3 x 200-240 V) [A]
Continuous
kVA (208 V AC) [kVA]
Max. cable size:
(line, motor, brake)
[mm
2
/AWG]
2)
Continuous
(3 x 200-240 V) [A]
Intermittent
(3 x 200-240 V) [A]
1)
Max. pre-fuses
Environment
Estimated power loss
at rated max. load [W]
Weight enclosure IP 20 [kg]
Weight enclosure IP 21 [kg]
Weight enclosure IP 55 [kg]
Weight enclosure IP 66 [kg]
3)
Efficiency
MG.11.B4.22 - VLT
B1
B1
B1
B1
B1
B1
P5K5
P7K5
5.5
7.5
7.5
10
24.2
30.8
26.6
33.9
8.7
11.1
10/7
22.0
28.0
24.2
30.8
63
63
[A]
269
310
4)
23
23
23
23
23
23
0.96
0.96
®
is a registered Danfoss trademark.
VLT
®
HVAC Drive Design Guide
B1
B2
B1
B2
B1
B2
P11K
P15K
11
15
15
20
46.2
59.4
50.8
65.3
16.6
21.4
35/2
42.0
54.0
46.2
59.4
63
80
447
602
23
27
23
27
23
27
0.96
0.96