Cisco ONS 15454 Manual page 55

Turning up a node
Hide thumbs Also See for ONS 15454:
Table of Contents

Advertisement

Turning Up a Node
Caution
Step 11
Thread the fiber cable through the second bend delimiter and out the appropriate side of the fiber-storage tray
as necessary.
Step 12
Route the fiber-optic cable through the vertical fiber guide as needed to reach the second ROADM shelf where
the second 32WSS is located.
Step 13
Route the fiber-optic cable through the shelf cutout and through the shelf cable routing channel as needed.
Step 14
Plug the end of the 3-meter fiber-optic cable into the EXP-RX port of the second 32WSS card.
Step 15
Plug one end of the second 3-meter fiber-optic cable into the EXP-TX connector on the second 32WSS card.
Step 16
Follow
port of the first 32WSS card.
Step 17
Close the fold-down doors located at the bottom of both shelf assemblies and slide the fiber-storage tray back
into its normal locked position.
Stop. You have completed this procedure.
NTP-G141 Installing Fiber-Optic Cables for Y-Cable Protection
Modules
Purpose
Tools/Equipment
Prerequisite Procedures
When you close the fiber-storage tray, the cables must not be pinched, and the cable bend radius
must be equal to or greater than the minimum radius that is recommended in your site specifications.
As you route each cable through the fiber-storage tray, make sure that adequate cable slack remains.
Step 7
through
Step 14
to connect the EXP-TX connector of the second 32WSS card to the EXP-RX
NTP-G141 Installing Fiber-Optic Cables for Y-Cable Protection Modules
This procedure installs and routes fiber-optic cables
from the client signal to the Y-cable protection module
(single mode or multimode), and from the Y-cable
module to the transponder node. Using one Y-cable
protection module, you can protect one client signal
with two TXP, MXP, AR_MXP, AR_XP, AR_XPE,
GE_XP, 10GE_XP, GE_XPE, 10GE_XPE, or
OTU2_XP cards, and two client signals with four
TXP, MXP, GE_XP, 10GE_XP, GE_XPE,
10GE_XPE, or OTU2_XP cards. You can use Y-cable
protection modules that you have installed in a
FleyLayer shelf, or Y-cable modules installed in a
Y-cable module tray.
Fiber-optic cables
Cisco Transport Planner Internal Connections Report
See
Cisco ONS 15454 Hardware Installation
• "DLP-G32 Install the Y-Cable Protection
Modules in the FlexLayer Shelf"
• "DLP-G377 Install the Y-Cable Protection
Modules in the Y-Cable Module Tray"
Guide:
Turning Up a Node
55