Installation; Installation Site And Environment; General; Restricted Locations - Alpha ESS Storion-SMILE-T10 Installation Manual

Indoor energy storage system
Hide thumbs Also See for Storion-SMILE-T10:
Table of Contents

Advertisement

INSTALLATION

1.5 Liability Limitation
Any product damage or property loss caused by the following conditions AlphaESS
does not assume any direct or indirect liability.
• Product modified, design changed or parts replaced without AlphaESS authoriza-
tion;
• Changes, or attempted repairs and erasing of series number or seals by non
AlphaESS technician;
• System design and installation are not in compliance with standards and regula-
tions;
• Failure to comply with the local safety regulations (VDE for DE, SAA for AU);
• Transport damage (including painting scratch caused by rubbing inside packaging
during shipping). A claim should be made directly to shipping or insurance company
in this case as soon as the container/packaging is unloaded and such damage is
identified;
• Failure to follow any/all of the user manual, the installation guide and the mainte-
nance regulations;
• Improper use or misuse of the device;
• Insufficient ventilation of the device;
• The maintenance procedures relating to the product have not been followed to an
acceptable standard;
• Force majeure (violent or stormy weather, lightning, overvoltage, fire etc.);
• Damages caused by any external factors.
02
INSTALLATION
This Manual introduces the basic steps on how to install and set up Alpha ESS
Storion-SMILE-T10
M4856-S is a sealed component with no access to battery terminals or cell components
within module.
NOTE: please pay attention to unpacking the battery, the worst case is that some
components could be damaged.

2.1 Installation Site and Environment

2.1.1 General

he M4856-S has two versions, one is indoor, and another is outdoor. The SMILE-T10
energy storage system (indoor version) can only be installed in an indoor location. The
SMILE-T10 energy storage system (outdoor version) can be installed in an outdoor or an
indoor location.
The SMILE-T10 systems should be installed in a room, where access to SMILE-T10 is not
obstructed by the structure of the building, fixtures and fittings within the room.
The SMILE-T10 adopts to natural ventilation. The location should be clean, dry and
adequately ventilated. The room's entry doors and panels shall open in the direction of
egress and allow unobstructed access to the SMILE-T10 for installation and maintenance
purposes.
09
10
The following location are not allowed for installation:
• habitable rooms;
• in ceiling spaces;
• wall cavities;
• on roofs not specifically deemed suitable;
• areas of access/egress;
• under stairways;
• under access walkways;
• sites where the freezing point is reached, like garages, carports or other places;
• sites with humidity and condensation over 85%;
• sites which are salty and where humid air can penetrate;
• earthquake areas –additional security measures are required here;
• sites that are higher than 3000 meters above the sea level;
• sites with explosive atmosphere;
• sites with direct sunlight;
• sites with extreme change of ambient temperature;
• wet rooms;
• sites with highly flammable materials or gases; or
• sites with a potentially explosive atmosphere;

2.1.2 Restricted Locations

Where the SMILE-T10 is located on or within 300mm of the wall or structure separat-
ing it from the habitable room, the barrier shall extend —
(i) 1000 mm beyond the vertical sides of the SMILE-T10;
(ii) 300 mm above the SMILE-T10; and
(iii) To the extent of the bottom of the SMILE-T10.
Please refer to Figure 10
Figure 10 Distancelimit of Installation to Neighboring Objects
INSTALLATION