EMS INTRODUCTION AND SET UP

3.2 Switch off

System shall be turned off in the correct sequence to avoid any damage.
Step 1 Remove the front panel of the inverter and HV50056
Step 2 If backup load is applied, turn off the Backup AC breaker.
Step 3 Turn off the MCCB of HV50056.
Step 4 Turn off the PV switch of the inverter
Step 5 Turn off the On-grid AC breaker.
04
EMS INTRODUCTION AND SET UP

4.1 Function Description

Figure 42 SMILE-T10 EMS Interface
Item
Status
Name
A
Fault
B
Battery
C
Normal
D
Internet
Description
ON: Fault
OFF: No Fault
ON: Battery communication is OK
OFF: Battery communication is lost
ON: System works normally
OFF: System is abnormal or warning
ON: System is communicating with server
OFF: System is not communicating with server
31
32
Object
Name
E
Button
F
Function
G
H
I
LCD Screen
4.2 Setting
Figure 43 Password Interface
Step 1 Click setting and enter the
password.
The installation's password is four-digit
password: 1111, after the password is
correctly entered, you shall be at the main
Setting interface (administrator
permissions).
Figure 43 Password Interface
Step 3 Click Solar to set the Solar relevant
information.
EMS INTRODUCTION AND SET UP
Description
Return Button: Escape from current interface or function
Up button: Move cursor to upside or increase value.
Down Button: Move cursor to downside or decrease value.
ENT Button: Confirm the selection.
Display the information of the inverter in this LCD screen.
Figure 44 Setting Menu
Step 2 Click Function to enter function
setting.
Figure 46 Solar Setting Interface
Step 4 Set PV capacity, the total capacity
of PV capacity of T10-INV and PV inverter
(if it is installed).