Acr10R Meter (If Applicable); Meter Setting - Alpha ESS Storion-SMILE-T10 Installation Manual

Indoor energy storage system
Hide thumbs Also See for Storion-SMILE-T10:
Table of Contents

Advertisement

INSTALLATION

2.4.2 ACR10R Meter (If Applicable)

A PV meter will be applied in an
AC/hybrid system.
Figure 41 ACR10R with CT Connection (without Meter Plug)
Note: When connecting CTs, pay attention to CT arrow directions, please refer to
Figure 41.
27
28

2.4.3 Meter setting

2.4.3.1 ADL3000
Step 1 The initial interface of the meter
(normal working interface) is as shown
below:
Step 3 Click the "Enter" button to enter
the following interface and press the up
and down arrow keys to enter the
password 0001;
Step 5 Click the "Enter" button again to
enter the address interface:
Step 7 Click the "Enter" button and the
address setting is completed.
INSTALLATION
Step 2 Click the "SET" button to enter the
password interface:
Step 4 Click the "Enter" button and the
password input is complete.
Step 6 Click the "Enter" button to enter the
following interface, press the up and down
arrow keys to set the meter address, the
Grid meter (DC, AC and Hybrid system)
address is set to 001, and the PV meter (AC
and Hybrid system) address is set to 002.
Step 8 Click the "SET" button to enter the
following interface:

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Smile-t10-invHv50056M4856-s

Table of Contents