2 Installation
2.3.2 Installation Standards
2.3.2
Installation Standards
Observe the standards for mounting SERVOPACKs in control panels, including those
for the mounting SERVOPACKs side by side in one control panel as shown in the
following illustration.
• SERVOPACK Mounting Orientation
Mount the SERVOPACK vertically to the wall, with the front panel facing out.
• Cooling
Refer to the following diagram and leave sufficient space for cooling by fans and nat-
ural convection.
• Mounting SERVOPACKs Side by Side in a Control Panel
Leave sufficient space on each side and at the top and the bottom of each SERVO-
PACK. Space between SERVOPACKs differs with the cooling method as shown in
the following table.
Cooling Method
Natural Convection
∗ When the space between SERVOPACKs is less than 10 mm, select fans that will circulate air
at a wind velocity of 0.2 m/s or more when a wind gauge is installed 10 mm away from the
bottom of the SERVOPACK.
• Inside the Control Panel
The conditions inside the control panel should be the same as the environmental con-
ditions of the SERVOPACK. Refer to 2.1.2 SERVOPACK Installation Environment.
2-10
Fan
30 mm
or more
∗ Mounting differs with cooling method.
Per Side
*
1 mm or more
Fan
10 mm or more
Fan
10 mm
10 mm
or more*
or more*
Top and Bottom
40 mm or more
40 mm or more
40 mm or more