4.7

Technical Data

Technical data
Bus system
Ethernet connection
Fieldbus protocol
Redundancy protocol
Input data width
Output data width
Parameter data
Transfer rate
Fast startup
Shared device/input
Addressing
GSDML
Net load
I&M data
Inputs
Number
Input type
Low input voltage
High input voltage
Input filter
Sensor supply
Sensor connection
Reverse polarity protection
Short circuit protection
Surge protection
Outputs
Number
Output type
Load type
Max. output current
per channel
per module
Breaking energy (inductive)
Switching frequency
Ohmic load (min. 12 Ω)
Inductive load (DC 13)
Lamp load (48 W)
Actuator connection
Short-circuit-proof
Protective circuit
2599890000/01/03.2020
UR67-PN-V14-CU-16DI-12
UR67-PN-V14-CU-8DIDO-12
(2599680000)
2x V14 PushPull RJ45 data connectors (AIDA)
16
0
0.2 Hz without free-wheeling diode, 500 Hz with suitable free-wheeling diode
Constant current with thermal cutout; configurable parameters: automatic restart / malfunction acknowledgement
UR67-PN-V14-POF-16DI-12
(2599670000)
(2599700000)
2x V14 PushPull SC-RJ POF data connectors (AIDA)
PROFINET IO (RT / IRT), V2.3, Conformance Class C
MRP
max. 10 byte
max. 4 byte
max. 16 byte
Max. 100 Mbps
< 500 ms
yes, for 2 control units
DCP
GSDML-V2.33-WI-UR67PN-20190118.xml
Class III as per Security Level 1 Test (PNO)
I&M 0-4
8
Sourcing, type 2 as per IEC 61131-2
< +5 V with regard to 0 V of input voltage U
> +11 V with regard to 0 V of input voltage U
Input delay, adjustable from 0 to 20 ms
500 mA
2-wire + FE, 3-wire + FE via M12, 5-pin A-coded
yes
Sensor supply: multifuse, automatic restart after tripping
Yes
8
Sourcing
Ohmic, inductive, lamp load
2 A
16 A
150 mJ per channel
500 Hz
10 Hz
2-wire + FE via M12, 5-pin A-coded
yes
Manual UR67-PROFINET-V14
4 Module descriptions | Technical Data
UR67-PN-V14-POF-8DIDO-12
(2599690000)
16
8
S1
S1
0
8
14

Advertisement