4.5

Technical data

UR20-4COM-IO-Link
System data
Data (coupler dependent)
Interface
System bus transfer rate
Digital inputs
Number
Sensor types
Low input voltage
High input voltage
IO-Link interfaces
Number
Type
Transfer rate
Output current C/Q (in DO mode)
Input type C/Q (in DI mode)
1)
Output current L+
Line break detection
Short-circuit-proof
Module diagnosis
Individual channel diagnosis
Supply
Supply voltage
Current consumption from system current path I
Current consumption from input current path I
General data
Type of connection
Dimensions
Weight (operational status)
Protection class (IEC 60529)
1) If C/Q is used as digital input, the connected device shall only be supplied via the L+ and L- connections of the respective channel.
2) Higher altitudes are possible when particular deratings are considered. Please contact your responsible Weidmüller company as needed.
2547720000/03/09.2019
see Chapter 8
u-remote system bus
48 MBit/s
4
Typ 1 and Typ 3 acc. IEC 61131-2
< 5 V
> 11 V
4
IO-Link as per IEC 61131-9
4,8 kBaud / 38,4 kBaud / 230,4 kBaud, depending on the connected IO-Link device
0,1 A
Typ 1 and Typ 3 acc. IEC 61131-2
0.5 A per channel, total max. 2 A
yes
yes
yes
yes
24 V DC +20 %/-15 %
8 mA
SYS
25 mA + sensor supply
IN
"PUSH IN"
Height
Width
Depth
88 g
IP 20
Manual Communication module UR20-4COM-IO-LINK
4 Module description | Technical data
Single-wired, fine-wired
Conductor cross-section 0.14 – 1.5 mm
2
120.0 mm / 4.72" (with release lever: 128.0 mm / 5.04")
11.5 mm / 0.45"
76.0 mm / 2.99"
(AWG 16 – 26)
15