Web Server; Connecting And Starting Up The Web Server; Getting To Know And Setting Up The Web Server - Weidmuller UR67 Series Manual

Remote-i/o-system u-remote, i/o-modules ip67 profinet-v14
Hide thumbs Also See for UR67 Series:
Table of Contents

Advertisement

9

Web server

The web server is used to display the UR67 module on a
connected PC. This allows you to carry out the following
functions for test purposes or during commissioning or ser-
vice work:
– Access the module status
– Display and change the module parameters
– Access diagnostic information
– Reset the device to factory settings
– Operate the module in Force mode for testing purposes
– Updating firmware
9.1

Connecting and starting up the web server

Web browsers
The web server can be used with the following web brows-
ers:
– Mozilla Firefox 64 or higher
– Google Chrome 71 or higher
Screen resolution
When working with the web server, we recommend using a
screen resolution of 1280 x 800 or higher, but at least 768 x
800. The operator front-end is displayed optimally when the
browser window is maximised.
Starting the web server
The module must be completely assembled and connected
to the power.
▶ Make sure that the PC and the module are connected via
Ethernet.
The modules are delivered with the IP address
0.0.0.0. A free IP address must be assigned to
the module before the web server can be used
(e.g.using an engineering tool). The PC and the
module must be in the same subnet.
▶ Open one of the browsers listed above.
▶ In the address line, enter the IP address of the module.
The web server will then be started up. The connected mod-
ule will be displayed.
If the web server does not start up:
▶ Clear the browser cache. Deleting only the his-
tory is not a sufficient measure in this
instance.
▶ Restart the web server.
▶ Check the module IP address and check
whether the correct subnet has been selected.
2599890000/01/03.2020
9 Web server | Connecting and starting up the web server
9.2
Getting to know and setting up the web
server
Module overview
The overview page is displayed every time the web server is
started up.
2
1
Overview page with operating elements
1
Module detailed view
2
Navigation bar
3
Menu bar
4
Display area
Manual UR67-PROFINET-V14
3
4
35

Advertisement

Table of Contents
loading

Table of Contents