Fieldbus Features; Web Server; Accessories - Weidmuller UR67 Series Manual

Remote-i/o-system u-remote, i/o-modules ip67 profinet-v14
Hide thumbs Also See for UR67 Series:
Table of Contents

Advertisement

3.1

Fieldbus features

MAC addresses
Each module has three unique MAC addresses assigned by
the manufacturer that cannot be changed by the user (one
for the module and two for the Ethernet ports). The MAC ad-
dress of the module is imprinted on the module itself.
Integrated Ethernet switch
The integrated Ethernet cut-through switch with two con-
nections makes it possible to set up ring topologies and line
topologies.
PROFINET product features
The UR67-PN-V14 modules support the PROFINET IO device
IRT (Isochronous Real-Time). This means that process data
can be transferred in real-time.
The UR67-PN-V14 modules support the following PROFINET
functions:
– DCP for the automatic assignment of IP addresses
– Fast start-up for prioritised start-up
– Device replacement without interchangeable medium /
PG for the replacement of devices without re-configura-
tion
– LLDP for the detection of devices in the vicinity (neigh-
bouring device detection)
– MRP for the implementation of redundant PROFINET net-
works without additional switches
– Shared Device for the flexible assignment of channels
and modules to different control units
– SNMP for the monitoring of network components
Alarm and diagnostic messages
The modules offer extended alarm and diagnostic messages.
– Module diagnostics
– Individual channel diagnostics
– Fibre-optic cable diagnostics (only with UR67-PN-V14-
POF)
Device description files
A device description file is needed for the configuration and
parameterisation of the module in the engineering tool.
– PROFINET: modular GSDML file
You can download the current device description
files from the Weidmüller website.
2599890000/01/03.2020
3.2

Web server

The web server can be used to display the UR67-PN-V14
module on a connected PC. This allows you to execute the
following functions for test purposes or during commission-
ing or service work:
– Access the module status
– Display and change the module parameters
– Access diagnostic information
– Operate the module in Force mode for testing purposes
A description of the web server can be found in chapter 9.
3.3

Accessories

Protective caps
Degree of protection IP67 is only achieved when the module
is fully installed. Therefore, all connections not being used
must be fitted with protective caps. The dust caps included
with the module for the supply connections and the Ethernet
connections are not suitable for achieving degree of protec-
tion IP67.
Connection
Protective cap
M12
SAI-SK-M12-UNI 2029
V14 PushPull RJ45
IE-BP-V14P
V14 PushPull SC-RJ POF
IE-BP-V14P
PushPull Power
IE-BP-VAPP (IP 54)
Markers
Markers are required for the labelling of operating materials.
The markers can be printed using the Weidmüller PrintJet
ADVANCED (order no. 1324380000).
Markers
ESG 8/13.5/43.3 SAI AU
large markers 8/43.3 and small markers 8/13.5
Cable lugs
In order to select the correct cable lugs for attaching the FE
conductors, we recommend using the Weidmüller catalogue
6 or the product catalogue on Weidmüller website.
Cables and connections
In order to select the correct cables, we recommend using
the Weidmüller catalogue 8 and 9 or the product configura-
tor on the Weidmüller website.
Manual UR67-PROFINET-V14
3 System overview | Fieldbus features
Order No.
2330260000
1058310000
1058310000
1068930000
Order No.
1912130000
7

Advertisement

Table of Contents
loading