System overview

UR67-PN-V14-CU-X (2599670000, 2599680000)
UR67-PN-V14 modules for PROFINET
The UR67-PN-V14 modules are digital I/O modules that com-
municate via PROFINET.
The fully encapsulated metal housing means that the mod-
ules comply with degree of protection IP67.
The digital inputs comply with type 2 in accordance with
IEC 61131-2. For connections with digital inputs, a self-reset-
ting fuse limits the sensor supply current to 0.5 A per pin.
The output current is up to 2 A per channel. The output cir-
cuits are galvanically isolated from the rest of the network
and from the sensor electronics. The outputs are designed
with short circuit protection.
The modules with output functionality support a substitute
value function. This function can be used to set how an
output is to respond to an impaired or interrupted fieldbus
communication.
The UR67-PN-V14 modules differ with regard to their I/O
functionality and their Ethernet connections.
Module designation
UR67-PN-V14-CU-16DI-12
UR67-PN-V14-CU-8DIDO-12
UR67-PN-V14-POF-16DI-12
UR67-PN-V14-POF-8DIDO-12
2599890000/01/03.2020
Order number
Ethernet connection
2599680000
V14 PushPull RJ45
2599670000
V14 PushPull RJ45
2599700000
V14 PushPull SC-RJ POF
2599690000
V14 PushPull SC-RJ POF
UR67-PN-V14-POF-X (2599690000, 2599700000)
Status LEDs are assigned to the module and to each I/O con-
nection, and the colour and flashing behaviour of these LEDs
indicate the status of the connection (see chapter 8).
Number of digital inputs
16
8
16
8
Manual UR67-PROFINET-V14
3 System overview
Number of digital outputs
0
8
0
8