9.7

Resetting the module to factory settings

This function allows you to reset the module to its original
state upon delivery. The following data is reset as part of this
process:
– Parameters, incl. network parameters
– I&M data
The module is restarted during the reset process!
▶ Make sure that you are logged in.
▶ Click on ☰ in the menu bar.
▶ Click on Restore factory settings.
▶ Confirm by clicking on OK.
Resetting the module to factory settings
The module and the web server are restarted. The module
will once again be in the same state as it was when it was
initially delivered.
▶ Assign an IP address to the module again in order to
access the web server again.
2599890000/01/03.2020
9 Web server | Resetting the module to factory settings
9.8

Web server in Force mode

Enabling Force mode
Manipulation of the control unit!
In Force mode, the system may be manipu-
lated to such an extent that life-threatening
personal injury and material damage may
occur.
Only use Force mode if you are very familiar
with the connected system and always know
the consequences that your actions will have!
If Force mode is enabled when the fieldbus is
connected, a diagnostic alarm will be triggered.
Depending on the parameterised alarm behav-
iour, output process data may continue to be
transferred by the PLC and processed by the mod-
ule for all unforced output channels. All of the
forced output channels ignore the process data
and proceed exclusively according to the forced
values.
Input process data is always transferred regard-
less of whether it is simulated through forced
operations or whether it has been imported via
physical inputs.
If Force mode is enabled without a fieldbus con-
nection, the fieldbus interface will be deactivated
for the duration of forced operations. A new field-
bus connection can only be established again
once Force mode has been terminated.
Force mode allows you to carry out functional tests or pre-
configure the module prior to commissioning, even if no sen-
sors or actuators have been connected. To do so, you must
change the operating mode of the web server.
▶ Make sure that you are logged in.
▶ Click on Force in the menu bar.
▶ Confirm by clicking on OK.
Manual UR67-PROFINET-V14