7.3.6 To prevent the outdoor unit from falling over

ERGA04~08DAV3(A) + EHVH/X04+08S18+23DA/DJ3V+6V+9W7
Daikin Altherma 3 R F
4P618947-1 – 2020.03
c Drain hole insulation
Drain pan heater. You can use the drain pan heater option (EKDPH008CA) to
prevent freezing-up of the drain pan. For the installation instructions, see the
installation manual of the drain pan heater.
Non-heated drain tube. When using the drain pan heater without drain tube or
with a non-heated drain tube, remove the drain hole insulation (Item c on the
illustration).
INFORMATION
If you install the drain pan kit (with or without drain pan heater) in combination with
the low sound cover (EKLN08A1), different installation instructions apply for the
drain pan kit. See the installation manual of the low sound cover.
a
a Low sound cover
b Bottom parts of the low sound cover
c Drain pan kit
d Drain pan heater
In case the unit is installed in places where strong wind can tilt the unit, take
following measure:
1 Prepare 2 cables as indicated in the following illustration (field supply).
2 Place the 2 cables over the outdoor unit.
7
Installation
|
c
b
d
c
b
Installer reference guide
75