Underfloor heating or radiators – Wireless room thermostat
ERGA04~08DAV3(A) + EHVH/X04+08S18+23DA/DJ3V+6V+9W7
Daikin Altherma 3 R F
4P618947-1 – 2020.03
Setup
a
A Main leaving water temperature zone
B One single room
a Receiver for wireless external room thermostat
b Wireless external room thermostat
The underfloor heating or radiators are directly connected to the indoor unit.
The room temperature is controlled by the wireless external room thermostat
(optional equipment EKRTR1).
Configuration
Setting
Unit temperature control:
#: [2.9]
Code: [C-07]
Number of water temperature zones:
#: [4.4]
Code: [7-02]
External room thermostat for the main
zone:
#: [2.A]
Code: [C-05]
Benefits
Wireless. The Daikin external room thermostat is available in a wireless version.
Efficiency. Although the external room thermostat only sends ON/OFF signals, it
is specifically designed for the heat pump system.
Comfort. In case of underfloor heating, the wireless external room thermostat
prevents condensation on the floor during cooling operation by measuring the
room humidity.
5
A
B
b
1 (External room thermostat):
Unit operation is decided by the
external thermostat.
0 (Single zone): Main
1 (1 contact): When the used
external room thermostat or heat pump
convector can only send a thermo ON/
OFF condition. No separation between
heating or cooling demand.
Application guidelines
|
Value
Installer reference guide